Auxiliary Circuits; Eol Reference Programming; Figure 11: Wiring The Nac Outputs And Eol; Figure 12: Auxiliary Power Configuration - Bosch FPP-RNAC-8A-4C Operation And Installation Manual

Remote nac power supply
Table of Contents

Advertisement

Figure 11: Wiring the NAC outputs and EOL

A+
B+
B-
B+
A+
B+
B-
B+
A+
B+
B-
B+
A+
B+
B-
B+
1
1 K to 20 K
2
EOL*
3
Class B
4
Class A
EOL supplied by control panel manufacturer (Bosch P/N:
*
25899)
16
1
EOL
REF
O
U
2
T
N
N
N
P
N
U
T
3
4
4
O
U
T
N
N
P
U
T
3
O
U
T
P
U
T
2
O
U
T
P
U
T
1
FPP-RNAC-8A-4C | Operation and Installation Guide |
3.7.2

Auxiliary Circuits

The FPP-RNAC-8A-4C can be configured to supply
constant auxiliary power through its NAC outputs.
Reverse polarity connections of some
notification appliances might not be
detected by the FPP-RNAC-8A-4C NAC
supervision. Ensure that the notification
appliances are connected properly and
tested before installation is completed.
Use DIP Switch S1 positions 3, 4, 5, and 6 (refer to
Figure 12) to make the output always active. When
the output is configured as always active, the output
is unsupervised and no EOL is needed.
3.7.3

EOL Reference Programming

Add a resistor that matches the value of the EOL
used in the notification appliance circuit. This must be
in the range of 1 kΩ to 20 kΩ. If no resistor is present,
the RNAC defaults to the value of 2.2 kΩ.

Figure 12: Auxiliary Power Configuration

1
SYNC 2
SYNC 1
SYNC 0
NAC 4
2
NAC 3
NAC 2
NAC 1
3
CNTRL AL L
AC DELAY 1
4
AC DELAY 0
5
OPTION
ADDRESS
1
Configure SYNC pattern
2
Configure outputs for NAC or power supply
3
Input control
4
AC delay setting
5
Option address bus
Bosch Security Systems, Inc. | 8/09 | F01U025431-02
OFF
ON
S1
0
SYNC 2
1
SYNC 1
2
SYNC 0
3
POWER 4
4
POWER 3
5
POWER 2
6
POWER 1
S2
0
CNTRL 2
1
AC DELAY 1
2
AC DELAY 0
3
4
OPTION
4
3
ADDRESS
5
2
6
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents