PROBLEM
6. Relay does not energize
A. Relay driver programmed on "Time"
B. Relay driver programmed on "Gallons"
7. Relay energized during regeneration
18
RELAY TROUBLESHOOTING
CAUSE
A. Programmed incorrectly
B. Defective relay, See figure below
C. Defective PC Board
D. Faulty wire connections between
PC board and relay
A. Programmed incorrectly
B. Faulty meter connection
C. Defective relay, See figure below
D. Defective PC Board
E. Faulty wire connections between
PC board and relay
A. Relay programmed as "on REGEN
gallons"
Relay operation while in error modes
1. Relays should turn off immediately whenever a Valve Error occurs.
2. Relays should remain on and continue to operate as programmed if a MAV Error
(106/107 or 116/117) occurs and the valve has already entered regen.
3. Relays should remain off, and not operate as programmed, if a MAV Error (106/107
or 116/117) occurs and the valve has not entered regen.
CORRECTION
A. Reprogram, see page 8
B. Replace Relay
C. Replace PC Board
D. Check and repair wire connections
A. Reprogram, see page 8
B. Repair or replace meter assembly
C. Replace Relay
D. Replace PC Board
E. Check and repair wire connections
A. Reprogram, see page 8