SYSTEM BOARD
STEP 9CS
ENABLED
SET
AUX MAV OFF
STEP 10CS
TRIGGER
SET
AUX MAV RECLAIM
STEP 11CS
TRIGGER
SET
AUX RECLAIM START
30:00
SET
AUX RECLAIM DURATION
6:00
SET
MAX RECLAIM 2 START
38:00
SET
RECLAIM 2 DURATION
15:00
SET
AUX MAV SEP SOURCE
STEP 14CS
TRIGGER
SET
14
STEP 9CS – Configuring the Control Valve to operate with the Hellenbrand SystemMate
Controller - Select System Board Enabled to link the Control Valve to the SystemMate Con-
troller. For communication between the Control Valve and the System Controller, a three wire
communication cable is required.
Press NEXT to go to Step 10CS. Press REGEN to return to previous step.
STEP 10CS – Use the  or  buttons to select one of the following:
• Reclaim – Allows water or regenerant reclaimation. Up to 3 reclaim events can be
programmed – See instructions below.
• Separate Source –Allows Auxiliary MAV to switch positions before the start of regeneration
and to switch back at the end of regeneration. See instructions in Step 14CS.
• Off - Factory Setting is Off
Press NEXT to go to Step 11CS when reclaim selected as trigger. Press REGEN to return to
previous step.
STEP 11CS – Use the  or  buttons to select reclaim as Aux MAV Trigger. This option is
usually done with softeners for brine reclaim but can be used to reclaim water used during
regeneration. Three reclaim events are possible. RECLAIM is one event. RECLAIM 2X is two
events and RECLAIM 3X is selected for 3 different reclaim events.
STEP 12CS – Only displays if reclamation of brine is enabled in Step 11CS. Use the
STEP 12CS
 or  buttons to select the number of minutes after the start of regeneration before
MIN
the MAV will divert the waste water from the plumbing drain receptacle to the storage
tank. Start of regeneration is defined as any mode that is not fill or softening.
Press NEXT to go to Step 13CS. Press REGEN to return to previous step.
STEP 13CS – Only displays if reclamation is enabled in Step 11CS. Use the  or 
STEP 13CS
buttons to select the number of minutes to divert the waste water to the storage tank.
MIN
After the minutes count down to zero the waste water will once again be diverted to
the plumbing drain receptacle. Press NEXT to program next reclamation event if more
than one selected. Press NEXT to go to Step 15CS is only one reclaim event desired.
Press REGEN to return to previous step.
Only displays if RECLAIM 2X is selected. Use the  or  buttons to select number of
minutes after start of regeneration for Aux MAV to divert waste water. Press NEXT to
MIN
program number of minutes for duration of second reclaim event. Use the  or  but-
tons to select number of minutes of duration of second reclaim event. Press NEXT to
program third reclaim event or to go to Step 15CS if not further reclaim required.
MIN
STEP 14CS – Separate source selection requires connection of motorized alternator valve
(MAV) to Auxiliary Drive two-pin connection on board.
Auxiliary MAV Drive set to operate with a Separate Source trigger. Auxiliary MAV transitions
to Bypass before the start of regen cycle #1, AFTER Alternator MAV motor transition. Auxiliary
MAV transitions back to Service at the completion of the last programmed regen cycle, once
the Valve Motor deactivates and BEFORE Alternator MAV transition (if scheduled). Auxiliary
MAV will NOT automatically return to Service while manually stepping valve through regen,
MAV will remain in Bypass until regen cycle end. Press NEXT to go to Step 15CS. Press
REGEN to return to previous step.