SLOTTED LATCHES (2)
a38-7216
COMPRESSOR
ACCESS
Fig. 3 — Compressor Access Panel with 2
Latches — 38APS040,050
BACK – EVAPORATOR END
Fig. 4 — Left Side Enclosure Panel —
30MP016-071
HOOK AND LOOP
STRIPS
BLANKET SLOT
ALIGNING WITH
SUCTION TUBE
Fig. 5 — Align Blanket Slots with Suction Tube
REMOVE LEFT SIDE
ENCLOSURE PANEL
a30-6066
COMPRESSOR
DISCHARGE LINE
TERMINAL BOX
BLANKET
SUCTION TUBE
6. Align the slots in the blanket with the suction tube on the
compressor. See Fig. 5.
7. Secure the blanket near suction tube with the hook and
loop strips. See Fig. 5.
8. Wrap the blanket around the compressor terminal box. See
Fig. 6.
For 30MP016 units with compressor insulation, cut out the
sound blanket around the compressor terminal box. The
compressor power leads should be placed outside the
sound blanket.
For 30MP050-071 units, the blanket will not cover the
compressor terminal box. See Fig. 7.
9. Attach the hook and loop strip on the vertical seam to se-
cure the blanket to the compressor. See Fig. 6.
10. For 30MP040,045 units, return control box to its original
position and tighten the 4 control box retaining screws on
each side of the unit.
11. Attach top flap of blanket with the hook and loop strip
while aligning the discharge opening with the discharge
line. See Fig. 6.
a. For units 38APS025-065, 38APD025-060, and
30RAP018-060: All wires pass through top cover
seam.
b. For unit 38APD070-130: 'B' Circuit wires pass
through top cover seam. 'A' Circuit wires pass under
the blanket.
c. For units 30MP016-045, 30RAP011,016, and
30RAP070-150: All wires pass under the blanket.
Except 30MP016 with compressor insulation as
noted in Step 8.
d. For units 30MP050-071: The wires pass outside the
blanket, the terminal box is outside the blanket, and
there is a cutout for the oil equalizer line. See Fig. 7
for 30MP050-071 units.
12. For 30RAP100-150 units, install the sound blanket cap by
aligning the discharge opening with the discharge line and
attaching the cap with the hook and loop strip to the sound
blanket.
13. Repeat Steps 3 through 12 for installation of sound blanket
to all compressors.
14. Replace the access panel by reversing the procedure in Step
3 or Step 4, if necessary.
15. Restore power.