Integrated Heat Exchanger With Condensing Technology - Eco6 - Bosch UT-L 1 Technical Manual

Table of Contents

Advertisement

16 | Technical description
3.3.3
Integrated heat exchanger with condensing technology — ECO6
740
560
200
Fig. 10 Integrated heat exchanger with condensing technology — ECO 6
D03.000 Flue gas connecting branch
W32.000 Flue gas heat exchanger
W32.008 Inspection aperture on the flue gas side
W32.507 Connection for flue gas condensate
W32.509 Connection for water inlet
W32.510 Connection for water outlet
Shipping weight
Heat
exchanger
1 bundle
ECO 6
[~kg]
390 / 260
90
510 / 335
110
600 / 385
140
690 / 460
170
750 / 485
190
850 / 560
230
890 / 610
250
930 / 635
270
1000 / 685
290
1110 / 760
320
1300 / 885
400
1350 / 985
460
1550 / 1060
540
1600 / 1085
570
1750 / 1185
630
1900 / 1285
730
2050 / 1385
820
2200 / 1485
930
Table 8 Main dimensions
6 720 807 794 (2013/04)
1)
W32.008
Water
2 bundle
capacity
[~kg]
[mm]
140
10
180
15
220
20
260
26
310
29
360
37
400
42
440
46
470
52
520
64
650
85
750
98
880
119
950
125
1040
148
1210
173
1360
200
1550
228
1)
If the heat exchanger is designed to have several
bundle elements, the dimensions increase by
300 mm per bundle.
2)
For heat exchangers having a water inlet/water
outlet with an internal diameter of DN150, the
dimensions increase by 50 mm.
Measurements
2)
B 1
B 2
[mm]
[mm]
794
475
914
535
1004
580
1094
625
1154
655
1254
705
1294
725
1334
745
1404
780
1514
835
1704
930
1754
955
1954
1055
2004
1080
2154
1155
2304
1230
2454
1305
2604
1380
W32.000
W32.510
W32.509
D03.000
W32.507
6 720 803 977-12.1itl
Port
H 2
W32.506
[mm]
[DN]
474
1"
549
1"
599
1"
674
1"
699
1"
774
1"
824
1"
849
1"
899
2"
974
2"
1099
2"
1199
2"
1274
2"
1299
2"
1399
2"
1499
2"
1599
2"
1699
2"
UNIMAT