1.5 IEC 61850-3 & IEEE 1613
KGS-1260/I model has been enhanced and verified with compliance for IEC 61850-3 EMC, environmental and
mechanical requirements and IEEE 1613 requirements for power substations.
IEC 61850-3
IEC 61850-3 defines the general requirements, mainly regarding construction, design and environmental
conditions for utility communication and automation IEDs (intelligent electronic devices) and systems in
power plant and substation environments.
IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications Networking Devices in Electric
Power Substations
IEC 61850-3 EMC Test Specifications
IEC 61850-3
C 6.7.4 / EN 55022
C 6.7.4 / EN 55022
C 6.7.4 / EN 55022
C 6.7.3 / IEC 61000-4-2
C 6.7.3 / IEC 61000-4-3
C 6.7.3 / IEC 61000-4-4
C 6.7.3 / IEC 61000-4-5
C 6.7.3 / IEC 61000-4-6
C 6.7.3 / IEC 61000-4-8
C 6.7.3 / IEC 61000-4-11
C 6.7.3 / IEC 61000-4-16
C 6.7.3 / IEC 61000-4-17
C 6.7.3 / IEC 61000-4-18
C 6.7.3 / IEC 61000-4-29
IEC 61850-3 Environmental Test Specifications
IEC 61850-3
C 6.9.3
Dry heat - operational
C 6.9.3
Cold – operational
C 6.9.3
Change of temperature - operational
C 6.9.3
Damp heat - operational
Test
DC IN conducted emission
LAN conducted emission
Radiated emission
ESD
RS
EFT
Surge
CS
PFMF
AC-DIP
LFCS
DC-Ripple
Damped Oscillatory Wave
DC dips and interruption
Test
Level
Class A
Class A
Class A
+/-15kV Air, +/-8kV Contact
10V/m
DC IN & LAN: +/-4kV
DC IN +/-1kV, LAN +/-4kV
DC IN & LAN: 10V
100A/m, 1000A/m
N/A: No AC input in the device
DC IN & LAN: 30V/300V
10% of DC IN
DC IN & LAN: +/-2.5kV
DC IN 30% 0.1s, 0% 50ms
Specification
+70℃, 30%RH, 72hrs
-40℃, 72hrs
-40 ~ +75℃, 3hr, 6 cycles
+70℃, 95%RH, 72hrs