1MRK 511 440-UEN A
Section 5
Switchgear control unit SAM600-IO Version 2.2 IEC
Communication protocol manual
Supported services
IEC 61850-7-2 describes the services in the standard. IEC 61850-8-1 describes
how the services are applied in the communication. The conformance documents
contain the description of the supported services in the IED.
Services that are not mentioned in this chapter or in the conformance document are
not supported by the IED.
Data set
Define data sets by the SCD description.
Create data sets under LD0/LLN0.
For more information on data sets, see the PIXIT-related
documents.
Substitution
Substitution is supported for the respective DATA, according to IEC 61850-7-4,
that have the substitution attributes defined.
Setting group control block
There is only one setting group control block, which is located in LD0/LLN0
(Logical Device0/Logical Node 0).
Note that the actual number of used setting groups is defined by the
parameter MaxNoSetGRP in the function SETGRPS, which is
configured in PST in PCM600. But six setting groups is the
maximum and it cannot be exceeded.
Report control block
For properties about report control blocks, see PIXIT.
UnBuffered reporting as well as Buffered reporting is supported.
Generic object oriented substation event (GOOSE)
The structured GOOSE is supported. This means that the data sets can be defined
with FCDA as well as explicit attributes.
The supported data types to be published and received over GOOSE are binary
values, double point values, integer values and measured values, together with their
Section 5
Supported services
GUID-E08C91D7-A59B-478B-B39A-26E786591E2A v9
25