2.12 SENS setup
The 360° detection range is split into 3 sectors A – B – C of 120° each.
Sensitivity may be adjusted either for all three sectors or for each individual sector. Sectors may be completely deactivated.
Sensitivity setup for all 3 sectors sample sequence:
1 ¶ Maximum
2 ¶ High
Lock/
Sens
1
Unlock
3 ¶ Low
4 ¶ Minimum
Sensitivity setup for an individual sector sample sequence:
Red LED ¶ Sector A
Lock/
Green LED ¶ Sector B
Sens
Next
Unlock
Blue LED ¶ Sector C
Note: Individual sectors may be deactivated with «On/Off» (enabled 1x flash, disabled 2x flash). It is recommended to check the sensitivity in test mode after configuration. Each sector is thus
indicated by its respective LED colour code. The LED remains off in case of deactivated sectors.
2.13 Test Mode
Use test mode to check the device's detection area and sensitivity. Sectors detecting motion are identified by their respective LED colour flashing item 2.12.
Test mode sample sequence:
Lock/
Test
Lock/
test
Unlock
On/Off
Unlock

2.14 Reset to Factory Default

Perform the following steps to reset the presence detector to factory default, i.e. «Out-of-the-box» mode:
1. Press «Lock/Unlock» ¶ programming mode
2. Depress «Fact. set» for approx. 4 s until the green LED briefly switches off twice.
3. Press «Lock/Unlock» ¶ operating mode
The presence detector was returned to factory default and needs to be newly configured, i.e. all DALI ballasts need to be re-initialised item 2.2.
2.15 Burn-in Activation (100 hours)
The commissioning or replacement of fluorescent tubes requires a burn-in to optimise the luminaires operating life. The light output is set to 100% during burn-in. Daylight control is deactivated
as long as burn-in is active and motion is detected. The presence detector automatically returns to daylight control after burn-in is comleted. Light dimming is not possible during burn-in, neither
via push-buttons nor via P-IR remote control.
The number of hours during which burn-in was performed will be stored in case of power outages with the presence detector automatically resuming the operation as soon as power is back on.
Burn-in activity is displayed by the yellow LED flashing once per second if the presence detector is in operating mode.
yellow LED flashes 1x ¶ burn-in active
Lock/
Burn in
Unlock
yellow LED flashes 2x ¶ burn-in inactive
Note: In operation mode both LED (red and green) are archivated if burn-in is active.
2.16 Programming and selecting scenes
Programming scene 3 sample sequence:
1 ¶ Zone 1
2 ¶ Zone 2
Lock/
1
Dim-
Unlock
3 ¶ Zone 3
4 ¶ Zone 4
Selecting scene 3 sample sequence:
Green LED flashes 2x ¶ if scene is programmed
3
Note: A scene remains active (CLC switched off) for as long as movement is detected and during the delay time.
2.17 Setting of presence/absence light level (night, mode 4)
In mode 4 = corridor function controlled by day/night twilight switch (8) a fixed brightness level [in %] can be set for presence and absence at night (T4 = 230 V).
The night light level can be set in programming mode with Dim+/Dim-.
Increase absence night light level sample sequence:
Lock/
〉 green LED flashes
presence light level (night, mode 4)
4
Unlock
red LED flashes
absence light level (night, mode 4)
M. Züblin AG, Neue Winterthurerstrasse 30 , CH-8304 Wallisellen, www.zublin.ch
Installation instructions - Swiss Garde 360 Presence DALI Master A-Comfort 24 m
Lock/
Unlock
1 ¶ Maximum
2 ¶ High
1
3 ¶ Low
Unlock
4 ¶ Minimum
Lock/
Unlock
1 ¶ Scene 1
Setting level zones
2 ¶ Scene 2
3
1–4
3 ¶ Scene 3
4 ¶ Scene 4
Dim+
Lock/
Lock/
Unlock
Lock/
Unlock
9
Züblin Elektro GmbH, Marie-Curie-Strasse 2, DE-79618 Rheinfelden-Herten, www.zublin.de
Art.-Nr. 41750, 41751, 41761 - Edition 8-2017