INSTALLATION INSTRUCTIONS
EN
1. PRESENCE DETECTOR
1.1 Use
The presence detector controls the lighting of a daylight group (up to 3 zones) with constant lighting control and up to 2 secondary zones (On/Off). Additionally, the built-in relay allows for light
switching (secondary zone), HVAC control or isolating DALI devices from 230 V mains (cut-off). Manual control may be assumed either by external 230 V push-buttons (5) and/or low voltage
push-buttons via DALI input module (7) .
The presence detector detects the movements and the presence of persons using a passive infrared sensor (PIR). It reacts most sensitively to movements tangential to the monitored area. Move-
ments directly towards the presence detector are detected with a reduced sensitivity of approx. -50%. The switching duration is extended as long as movements (entire area) or the presence of
persons (presence area) are detected (1). The detection area may be increased with up to 10 Slave-detectors Swiss Garde 360 Presence DALI Slave A-Comfort 24 m.
The detector may also be used as a presence-independent constant light controller item 2.10.
The communication is based on the addressable DALI standard pursuant to EN 62386-101/102. The built-in DALI power supply provides up to 200 mA allowing for up to 64 DALI devices to be
connected.
Note: The maximum amount of DALI devices to be connected may be lower depending on power consumption.
The detector is designed for ceiling installation in offices, schools and public buildings.
1.2 Application
The presence detector may be operated in 4 different basic modes item 2.3
Mode 1: Constant light control (CLC) of a daylight group (zones 1 to 3) and up to 2 secondary zones (zones 3 and 4) as well as relay output for HVAC (9)
Mode 2: Constant light control (CLC) of a daylight group and secondary zones according to mode 1, but with relay output for lighting (zone 4) on/off (factory default) (10)
Mode 3: Constant light control (CLC) of a daylight group and secondary zones according to mode 1, but with relay output for cut-off (230 V isolation) (11)
Mode 4: CLC daylight group as Mode 1 but with corridor function controlled by Day/Night Twilight switches (8) to T4 (see below Day/Night *), relay output HVAC (12).
The secondary zones always switch independent of ambient light. Zone 1 always encompasses the luminaires closest to ambient light entry (windows), zone 2 includes those in the centre of
the room while zone represents the luminaires furthest away from daylight entry.
Mode 1 (HVAC relay)
Zone 1
x
Zone 2
x
Zone 3
x
Zone 4
x
Relay
Mode 3 (Cut-Off relay)
Zone 1
x
Zone 2
x
Zone 3
x
Zone 4
x
Relay
Day/Night*: activation with twilight switch (8) to T4 (open = day, 230 V = night). On the day (T4 = open) is the constant-light-control active with standby light.
During the night (T4 = 230 V) fixed brightness level in [%] for the presence and absence.
M. Züblin AG, Neue Winterthurerstrasse 30 , CH-8304 Wallisellen, www.zublin.ch
Installation instructions - Swiss Garde 360 Presence DALI Master A-Comfort 24 m
Mode 2 (Zone 4 relay)
x
x
x
Zone 1
x
x
x
Zone 2
(x)
x
(x)
Zone 3
x
Zone 4
x
Relay
Mode 4 (Corridor
day/night relay HVAC)
x
x
x
Zone 1
x
x
x
Zone 2
(x)
x
(x)
Zone 3
x
Day/Night*
x
Relay
x
x
x
x
x
x
x
(x)
x
x
x
x
x
x
ON
x
x
ON
x
(x)
x
x
x
3
Züblin Elektro GmbH, Marie-Curie-Strasse 2, DE-79618 Rheinfelden-Herten, www.zublin.de
Art.-Nr. 41750, 41751, 41761 - Edition 8-2017
x
x
(x)
x
x
(x)