Download Print this page

Zublin Swiss Garde 360 Presence DALI Master A-Comfort 24m Installation Instructions Manual page 8

Hide thumbs Also See for Swiss Garde 360 Presence DALI Master A-Comfort 24m:

Advertisement

2.8 Fine adjustment of preset LUX setpoint (daylight group only)
If certain daylight zones are too brightly or dimly lit, zone-specific adjustments can be made using the «Dim -» and «Dim +» push-buttons.
The fine adjustment of illuminance is, however, limited to a relatively narrow range.
Fine adjustment has to be performed on completion of calibration.
Increase daylight zone 2 illuminance sample sequence:
Green LED flashes as long as
Lock/
Lux
2
Dim +
Unlock
DIM+ push-button is pressed
Note: The detector works on the basis of actual daylight measurement. After the conclusion of programming with «Lock/Unlock», several minutes may pass before the constant light control
accepts the changes and adjusts the lighting.
2.9 Manual calibration
Recalibration of the zones in the daylight group can be initiated manually.
Calibration will automatically start during darkness (< 100 lx) where no movement is detected during the Time 1 delay time (typically at night) and the Time 4 standby lighting time has expired.
During calibration, the lighting is switched on for 2 min. Each zone is then individually
dimmed and the impact on the light measurement recorded.
Initiate calibration sample sequence:
Lock/
Lock/
Calib.
Unlock
Unlock
To verify that calibration has been performed, the status must be checked.
Check calibration status sample sequence:
Green LED flashes ¶ calibration performed
Status
Calib.
Red LED flashes ¶ calibration not yet performed (wait for darkness and no movement, Time 1 and Time 4 expired)
2.10 Time settings TIME
The following timer functions are available:
– Time 1: delay time lighting
– Time 2: HVAC
– Time 3: cut-off
– Time 4: standby lighting
Some timer functions may only be effective in certain modes item 1.2.
Set lighting delay time to 5 min sample sequence:
Lock/
100 lx/
Lock/
Time
1
Unlock
5 min
Unlock
Note: The detector may also be used as a presence-independent constant light controller by setting Time 1 to ∞.
The light will switch on after mains connection. OFF/ON via external push-button T1+2.
2.11 Deactivate standby lighting and set standby level
Standby lighting is activated for the set duration (Time 4) after the delay time (Time 1) has expired item 2.10. The standby lighting function may be deactivated.
Activate/deactivate standby lighting sample sequence:
Lock/
Lock/
Time
4
On/Off
Unlock
Unlock
Check the status of Timer 4 to ensure that standby lighting is deactivated.
Checking Timer 4 sample sequence:
green LED flashes 8x ¶ standby lighting off
Status
Time
4
green LED flashes <8x ¶ standby lighting on
The standby level is set in the programing mode by Dim+/Dim-. The level for standby light is 0.1 to 51%.
Pressing the Dim key briefly causes a change of 5%. If you press and hold the Dim switch, the value changes in the smallest increments (fine tuning).
Increase standby level sample sequence:
Lock/
green LED blinks while button DIM+ is pushed
Dim+
Unlock
M. Züblin AG, Neue Winterthurerstrasse 30 , CH-8304 Wallisellen, www.zublin.ch
Installation instructions - Swiss Garde 360 Presence DALI Master A-Comfort 24 m
Lock/
Unlock
Lock/
Unlock
8
Züblin Elektro GmbH, Marie-Curie-Strasse 2, DE-79618 Rheinfelden-Herten, www.zublin.de
Art.-Nr. 41750, 41751, 41761 - Edition 8-2017

Advertisement

loading

Related Products for Zublin Swiss Garde 360 Presence DALI Master A-Comfort 24m