Download Print this page

Automatic Calibration - Zublin Swiss Garde 360 Presence DALI Master A-Comfort 24m Installation Instructions Manual

Hide thumbs Also See for Swiss Garde 360 Presence DALI Master A-Comfort 24m:

Advertisement

2. P-IR REMOTE CONTROL (6)
Programming and configuration are done via the P-IR remote control DALI addressable Art.-Nr. 41934.
The detector's status is display by the green LED:
– Green LED off: detector in operating mode
– Green LED on: detector in programming mode
¶ Green LED flashing 1x: command received
Note: At the following example sequences for the remote control, a long or short
push of the button is distinguished by the line thickness of the button symbol:
Function
Time
Symbol
push-
Short push
0.5 s
button
push-
Long push
4 s
button
Note: See detail for further settings such corridor function, multi-zone, lighting scenes, status, etc. the manual „P-IR Manual DALI addressable 41934" on our product website.
2.1 Lock/Unlock
Press «Lock/Unlock» once to put the presence detector into programming mode. Repress «Lock/Unlock» to return to operating mode. The detector must be unlocked for all configuration except
for «Status», «1», «2», «3», «4»,
«On/Off», «Auto», «Dim +» and «Dim -». If no button is pushed for 5 min, the detector automatically returns to operating mode. Changes already made will be stored.
2.2 Initialisation of DALI devices
All DALI ballasts must be allocated to a lighting zone. Different lighting zones are required if a room is not evenly illuminated by ambient light (e.g. window front on one side). The detector individ-
ually adjusts the zones (constant light control) to achieve a homogenous room illumination. If a ballast is replaced after initialisation, the replacement ballast is automatically programmed with the
values of its predecessor. As from 2 defective ballasts, replacements must be allocated manually.
2 different types of zones exist:
– Daylight group (constant light control)
¶ Zone 1 always encompasses the luminaires closest to ambient light entry (windows), zone 2 includes those in the centre of the room while zone 3 represents the luminaires furthest away
from daylight entry. Zone 3 may also defined as a secondary zone, in which case only zones 1 and 2 belong to the daylight group.
– Secondary zone (On/Off)
¶ Zone 3 may be configured as part of the daylight group or as a secondary zone item 2.4. Zone 4 may be configured as On/Off, HVACE or cut-off item 1.2.
Allocation of zones, initialisation of luminaires
All DALI ballasts are addressed and allocated to zones as follows:
1. Connect mains power ¶ all ballasts switch on
2. Briefly press «Lock/Unlock» ¶ programming mode
3. Press «Init» for approx. 4 s ¶ green and red LEDs flash alternately
¶ automatic addressing starts1)
¶ each addressed light fitting is switched off
¶ addressing is finished as soon as all light fittings are switched off
4. First light fitting is switched on again
5. Define zone by pressing «1», «2», «3» or «4»2)
¶ Green LED flashing: zone allocation successful, red LED lighting: zone unsuccessful
6. Press «Next»
7. Next light fitting is switched on (return to step 5 until all light fittings have been allocated to a zone)
8. End addressing with «Lock/Unlock» ¶ operating mode
Note
: The red LED lights up for 1 s if the detector does not recognise a DALI ballast after 10 attempts. Check correct wiring and DALI ballast functionality.
1)
Note
: If the red LED briefly flashes during zone allocation, the DALI ballast could not be successfully allocated to a zone. Repeat zone allocation.
2)
Zone allocation sample sequence:
Lock/
Automatische Adressierung 〉
Init.
Unlock
If all DALI ballasts are addressed, the orange LED lights up after pressing «Next».
Assignment of the DALI relay module
¶ If the DALI relay module is to be used to switch conventional lighting, it is assigned in the addressing the same way as a lamp.
¶ If the DALI relay module is to function as an HVAC switch, it has to be addressed with "Mode" + "1".
¶ If the DALI relay module is to function as an cut-off switch, it has to be addressed with "Mode" + "3".

Automatic calibration

To ensure proper functioning of the constant light control, the detector must be calibrated.
Calibration will automatically start during darkness (< 100 lx) where no movement is detected during the Time 1 delay time (typically at night) and the Time 4 standby lighting time has expired.
Manual recalibration is recommended for unfurnished, newly furnished or reorganised spaces item 2.9.
M. Züblin AG, Neue Winterthurerstrasse 30 , CH-8304 Wallisellen, www.zublin.ch
Installation instructions - Swiss Garde 360 Presence DALI Master A-Comfort 24 m
1
Next
2
Next
6
Lock/
usw. 〉
〉 Automatic calibration
Unlock
Züblin Elektro GmbH, Marie-Curie-Strasse 2, DE-79618 Rheinfelden-Herten, www.zublin.de
Art.-Nr. 41750, 41751, 41761 - Edition 8-2017

Advertisement

loading

Related Products for Zublin Swiss Garde 360 Presence DALI Master A-Comfort 24m