29 - ECODESIGN

The sealing test must be carried out in compliance with EC regulation no. 517/2014 relating to certain greenhouse gases.
R410A, R134a and R407C are refrigerant gases with the following environmental impact:
1/ No impact on the ozone layer.
They have an ODP (Ozone Depletion Potential) index of 0
2/Impact on the greenhouse effect: Global Warming Potential (GWP) of each gas.
- R410A -------- GWP = 2088
- R407C -------- GWP = 1800
- R134a -------- GWP = 1430
- Users must ensure that periodic leak testing is carried out by qualified personnel based on the number of tonnes of CO
equivalent:
Without leak detection system
Test interval
With leak detection system
Refrigerant fluid
R407C (GWP = 1800)
charge*
* To find out the refrigerant charge and the number of tonnes of CO
unit's instruction manual.
- Users of any system subject to leak testing are required to keep a log of the quantities and types of fluids used, (added or
recovered), and to include the dates and results of leak tests, as well as the name of the technician and the technician's
company.
- A leak test must be carried out one month after any leak repairs.
- System users are responsible for collecting used refrigerant and having it recycled, regenerated or destroyed.
NA06.130 C
QG2
QC1
3 - 10
2 - 22
1 3 5
1 . 3 . 5
KC1
KG2
2-22
2 4 6
3-24
2 . 4 . 6
U1 V1 W1
MG2
MCO1
W2 U2 V2
R410A (GWP = 2088)
R134a (GWP = 1430)
QC2
2 - 22
1 3 5
KC2
2-24
2 4 6
LOW SPEED
WIRING
U1 V1 W1
MCO2
W2 U2 V2
W2
≥ 5 tCO2eq
Every 12 months
Every 24 months
≥ 2.39 kg
≥ 2.77 kg
≥ 3.49 kg
equivalent, refer to the technical characteristics in the
2
EN - 18
HIGH SPEED
U1
U2
V1
V2
W1
≥ 50 tCO2eq
Every 6 months
Every 12 months
≥ 23.9 kg
≥ 27.7 kg
≥ 34.9 kg
WIRING
W2
U1
U2
V1
V2
W1
2
≥ 500 tCO2eq
Every 3 months
Every 6 months
≥ 239 kg
≥ 277 kg
≥ 349 kg