CIAT MAGISTER Series Instruction Manual
Hide thumbs Also See for MAGISTER Series:

Advertisement

NA 14.54 B
10 - 2015
I n s t r u c t i o n m a n u a l

Advertisement

Table of Contents
loading

Summary of Contents for CIAT MAGISTER Series

  • Page 1 NA 14.54 B 10 - 2015 I n s t r u c t i o n m a n u a l...
  • Page 3: Table Of Contents

    SOMMAIRE PAGE 1 - INTRODUCTION 12 - COMMISSIONING 2 - RECEIPT OF GOODS 13 - MAINTENANCE 2.1 Checking the equipment 13-1 Filters 2.2 Identifying the equipment 13-2 Cooling coil 2.3 Documents 13-3 Electric heater 13-4 Humidifier 3 - SAFETY INSTRUCTIONS 13-5 Fans 4 - WARRANTY 13-6 Electrics box...
  • Page 4: Introduction

    Cooling capacity + water temperature used 30, av Jean Falconnier 01300 CULOZ (FRANCE) Tél.: 33-(0)4-79-42-42-42 www.ciat.com Made i n Fr anc e - Heating capacity + water temperature used (if heating coil option) + usage type (2 stages or TRIAC, if electric heater option)
  • Page 5: Documents

    2.3 Documents The following documents should be inside the cabinet: - Instruction manual - Control manual - Electrical diagram of the cabinet - Key to the electrical diagram - Dimensional drawing with connection diagram - Additional diagrams depending on options 3 - SAFETY INSTRUCTIONS Appropriate PPE (Personal Protective Equipment) when servicing the units...
  • Page 6: Weights And Dimensions

    Handling with a spreader beam and slings 1100 To be removed while handling, then replaced once the vertical unit is in place If the unit is lifted using a spreader beam and slings: - Protect the panels. - First remove all the caps covering the holes for the tubing on the lower section of the equipment. (Fig. 1). - Use tubing (Ø...
  • Page 7: Supply Air Type

    7 - SUPPLY AIR TYPE 3 supply air types: Fitting UNDER Fitting OVER Return air on front, supply Return air underneath, supply air Return air above air above except CW115 above except CW115 and DXA supply air underneath You must leave space for access to the front and to the right of the unit for maintenance and installation operations. For free air intake, there must be at least 500 mm above the unit.
  • Page 8: Location And Marking Of Components

    Under no circumstances should these vertical units be installed in an atmosphere that is: - Explosive - Flammable - Corrosive or dusty. Once at the place of installation, remove the wooden blocks. ● Different configuration options are possible:  The unit can be placed directly on the floor. In this case: The unit must be placed on a flat, smooth surface which is as level as possible (ratio of approx.
  • Page 9 CW40 to CW100, Over Assembly Electrics Box Cooling coil Control valve Electric heater (Heating coil) (option) Cooling coil Heating coil Filters (option) Condensate drain Additional cabinet pump (option) Control valve Humidifier Drain pump (option) (cooling coil) (option) CW115, Under Assembly Filters Electrics Box Cooling coil...
  • Page 10 DXA 59 to 85, Under Assembly Electrics Box Electrics Box Filters Direct Direct expansion coil expansion coil Electric Expansion valve heater (option) Liquid sight glass Solenoid valve Liquid tank access hatches Humidifier Additional cabinet Condensate drain Drain pump pump (optional) (option) DXA 59 to 85, Over Assembly Electrics Box...
  • Page 11: Connections

    10 - CONNECTIONS When following these steps, please consult the dimensional drawing and connection diagram as well as the wiring diagram found inside the vertical unit. 10.1 Hydraulic connections (CW) The hydraulic pipes must be routed through the plates provided for this purpose in the vertical unit frame. This is either done to the right of the unit or directly underneath.
  • Page 12: Refrigerant Connections (Dxa Model)

    A condensate drain pump option is available (see technical specifications in paragraph 12), provided that the humidifier option has not been requested. If the humidifier option is selected, the discharge must not drain into the unit's drain pan. To have a single discharge for both, connect the humidifier drain downstream of the unit's drain pan.
  • Page 13 Remote control + fault summary 3-ph 400V-50Hz +E power supply Note: Electrical and refrigerant connections not supplied by CIAT. Table of the maximum lengths for refrigerant connections The tables below show the permitted lengths for the pipers and the corresponding maximum height difference.
  • Page 14: Electrical Connections

    DXA 59 + 2 CD 100/7/8'' liquid line, 1''1/8 gas line Total length (m) Height difference (m) DXA 65 + 2 CD 120/7/8'' liquid line, 1''1/8 gas line Total length (m) Height difference (m) DXA 70 + 2 CD 120/7/8'' liquid line, 1''3/8 gas line Total length (m) Height difference (m) DXA 85 + 2 CD 150/7/8'' liquid line, 1''3/8 gas line...
  • Page 15 Table of currents (CW) CW 40 CW 53 CW 78 CW 100 CW 115 Voltage (V) Fan motor assembly Power (kW) 10,8 14,7 Current (A) Control circuit (transformer) Voltage (V) Current (A) Voltage (V) Humidifier (option) Power (kW) Current (A) Voltage (V) Power (kW) 33,6...
  • Page 16 For the indoor unit/outdoor unit electrical connections please see the wiring diagram. Recommendations concerning electrical connections of the indoor unit. Connect the indoor unit so that the main power supply comes from underneath the unit. Either on the right side of the unit (1 or 2) or from underneath (3). If using a cased base, pass it through one of the grommets on the right side intended for this purpose (See technical characteristics in paragraph 12.2.5).
  • Page 17: Technical Specifications

    11.1 Basic component 11.1.1 Control The vertical units are equipped with an automatic CIAT control: µAIR CONNECT2. CIAT µ Air Connect 2 The heart of the vertical unit, this manages the unit and ensures it functions correctly. It is incorporated into the display and is mandatory for DXA models.
  • Page 18 • On CW115 and DXA 59 to 85 vertical units: progressive 0-10V control. - Without control (CW only) • Progressive 0-10V control via a manual voltage potentiometer located inside the electrics box (graduated from 0 to 100%) CHILLED WATER CW 40 CW 53 CW 78 CW 100...
  • Page 19: Cooling Coil: Cw Model

    11.1.3 Cooling Coil: CW model Make sure that the chilled water supply pipes are insulated. Moderately tighten the coil supply connections to avoid damaging the manifolds The coil is regulated by a two-way or three-way valve equipped with a 0-10V servomotor (mounted and connected) ●...
  • Page 20 - Every 6 months for units containing 30 to 300 kg of refrigerant. - Every 3 months for units containing more than 300 kg of refrigerant. (Implementation of leak detection system) - For all systems which contain over 3 kg of refrigerant (2 kg in France), users are required to keep a log of the quantities and types of fluids used in, added to and recovered from the system, as well as the dates and results of the sealing tests.
  • Page 21: Filter

    11.1.5 Filter G4 filters: F7 filters: Thickness: 48 mm Thickness: 48 mm Efficiency: 90% gravimetric Efficiency: 85% opacimetric Filtering surface: 2 x the face area Filtering surface: 17 x the face area Fire rating: M1 Fire rating: M1 CHILLED WATER CW 40 CW 53 CW 78...
  • Page 22: Electric Heater

    The coil is adjusted by a two-way or four-way valve equipped with a 0-10V servomotor (mounted and connected). Coil specifications: HOT WATER CW 40 CW 53 CW 78 CW 100 Number of coils Coil (1 row) Capacity (l) 3.82 4.92 6.29 6.29 HEATING COIL...
  • Page 23: Humidifier

    To drain it, carry out siphoning. Warning: the water temperature can reach 100°C. • If the option without the µRC2.1 (CIAT) control has been chosen, a display can be found the cabinet, and which can be used to control the humidifier.
  • Page 24: Condensate Drain Pump

    (in l/h) Connect a Ø 10 int (3/8") flexible tube (not supplied by CIAT) to the pump discharge. For OVER models (3 and 5), if using a spreader beam and slings, the PVC tube will not be directly connected to the pump, for handling reasons.
  • Page 25: Bases

    11.2.5 Bases: • Support base: Adjustable feet For supply air through a raised floor. The height can be adjusted from 250 mm to a maximum of 610 mm. Adjustment screws are provided with the base for adjustment on site. Do not forget to stick the adhesive seal provided to the aluminium frame of the base to ensure tightness. •...
  • Page 26: Plenums

    Side hatches for pipe connection (hydraulic or refrigerant connection) and damper servomotor access, as well as a grommet for the power supply cable. 11.2.6 Plenums: • Supply air/intake plenum (H450 mm): Grommet for control cable routing or for master/slave management, as well as room sensor cables.
  • Page 27: Intake Damper On The Vertical Unit

    See electrical diagram for connection. Operation: A filter must be installed upstream on the fresh air side (type F7, not provided by CIAT and at customer's expense) so that the indoor air is not adversely affected. The option allows cooling to be carried out using outdoor air (fresh air), in accordance with the temperature and humidity conditions, to decrease the room temperature.
  • Page 28 Dimensions of the housing (with mounting support) Connectors Inside the front cover Mobile front panel Rear fixed housing Output terminal Supply Autozero block Left-hand Solenoid valve terminal block switch (CP111 only) Connection Right-hand switch LCC-S Packing box Pressure connections Electrical connections (as per NFC15-100 standards) See wiring diagram for connection Autozero To perform an Autozero, disconnect the tubes from the 2 pressure connections and press the "Autozero"...
  • Page 29 Configuration To configure the sensor, switch it off and enter the desired settings by moving the switches as described below. Once the settings have been configured, switch the sensor back on. To configure the sensor, undo the 4 screws on the housing and open it. The switches allowing for various settings are then accessible. Measurement scope settings - left-hand switch Switch Measurement...
  • Page 30: Lon Gateway

    - Temperature or temperature and humidity room sensors: The room sensors are mounted on a wall in the room to be regulated. The sensors are provided at the back of the vertical unit. For connections, please see the wiring diagram and the recommendations in paragraph 11.3. - Changeover control Surface-mounted onto the hydraulic circuit.
  • Page 31: Maintenance

    13 - MAINTENANCE The doors may be removed to facilitate access to all components (see removal diagram below) Open the doors. Pull out the pin and remove the hinge (Detail B). Lift off the door (Detail C). EN - 29 N 14.54 B...
  • Page 32: Filters

    13-1 Filters Check the filters frequently when commissioning the unit. The rate at which they will clog will depend on how well the air circuits were cleaned. Frequency of servicing The filter life depends essentially on the amount of dust in the air and the efficiency of the filtration system. The filtration quality cannot be maintained if the filter medium has been damaged during maintenance.
  • Page 33: Cooling Coil

    ▪ For filter sizes CW 115 and DXA 59 to 85 - Unscrew the clamps on the bottom of the filter (detail A) - Remove the filter by pulling up the tab on the top of the filter (detail B) Replace the used filters by new filters.
  • Page 34: Humidifier

    DXA 59 to 85 Electric heater Cleaning procedure: Remove the filters as instructed above, To avoid damaging the blower nozzle, make sure that it is not too close to the finned surface. 13-4 Humidifier Maintenance Clean the humidifier once a year and replace its tank. Cleaning or replacing the steam tank This operation is necessary when the deposits that form on the active surface of the electrodes prevent the correct flow of current (alarms E08, E06).
  • Page 35: Fans

    Supply valve CHARGING UNIT Flow regulator If the humidifier malfunctions (no steam produced), Check the conductivity of the water: it must be between 350 and 1250 µS/cm. In case of repeated scaling, check the water hardness. 15°F<TH<30°F. Filling solenoid valve Water top-up Drain pump Water drainage...
  • Page 36 Quick connectors (B) - Disconnect the quick connectors (figure B) for each fan motor assembly - Slide shims/supports under the FMAs to support them. Rear screw Rear screw Front screw Front screw - Remove the front screws - Gently unscrew the rear screws so that the FMAs do not fall out and so that they allow the FMAs to be removed by moving them forwards, as shown in figure C.
  • Page 37 Fitting OVER - Remove the screws on the fan access hatches and remove the hatches (figure A) Screws Quick-release connector - Disconnect the quick-release connectors (figure B) for each FMA. - Then unscrew the 4 screws per FMA that are situated level with the arches. - When refitting the FMA(s), follow the steps in reverse order and ensure the FMA screws are sufficiently tightened.
  • Page 38 Size CW115 - Fan access: remove the 6 screws from the fan access hatch (B) - Removing the lateral panels from the fans (A): - Remove the 4 screws (A) from the uprights then remove the uprights - Remove the screws from the fan removal panel (C), - Remove the fan attachment screws (D).
  • Page 39 DXA 59 to DXA 85 Fitting OVER Accessing and removing the fans: - Undo the screws for the fan access hatch and remove them (A) - Remove the screws and take off the trim strips (rep.B) - Remove the screws from the deflector and remove the deflector (C) - Remove the FMA retaining nuts (D) (located under the retaining arches) - When refitting the FMAs, make sure the nuts are torque tightened to 40 Nm.
  • Page 40 Fitting UNDER Accessing and removing the fans: - Undo the screws for the fan access hatches and remove the hatches (A) - Remove the screws and take off the trim strips (rep.B) - Slide shims/supports under the FMAs to support them, - Remove the FMA retaining nuts (C) EN - 38 N 14.54 B...
  • Page 41: Electrics Box 39 En

    Control check Filter check Leak test This document is not legally binding. As part of its policy for continual product improvement, CIAT reserves the right to make any technical modification it considers necessary without prior notice. EN - 39 N 14.54 B...
  • Page 42 EN - 40 N 14.54 B...
  • Page 44 Tel. : 08 11 65 98 98 - Fax : 08 26 10 13 63 (0,15 € / mn) Non-contractual document. With the thought of material improvement always in mind, CIAT reserves the right, without notice to proceed with any technical modification. Siège social Avenue Jean Falconnier B.P.

Table of Contents