5 x 16a relay & open protocol controller

Advertisement

installation steps
1. Mount the device on a DIN rail inside an approved enclosure.
2. Calculate loads to ensure any channels are not overloaded, then connect loads to the output channels. The maximum
loading of this device is as follows:
Maximum Channel Load: 16A 230V AC
Total Box Load: 80A
Connect supply and load cables to each channel. Note that this device must have an individual supply circuit for each
channel. The supply circuits can be on any phase. Note that loads must have a Neutral (1 Phase or 3 Phase Star), Delta
wiring is not supported.
3. 5 x Control Outputs, each selectable to;
- DALI broadcast: max 10 DALI loads per channel.
- DALI addressed: max 10 DALI loads per channel.
- 1-10V: max 10mA Sink or Source per channel.
- DSI: max 10 DSI loads per channel.
4. Connect a single phase 0.15A feed to the control circuit supply terminals. This device must be earthed.
5. Connect data cables to the device as per diagrams below.
6. If the Auxiliary input is to be used, connect a dry contact device in between the AUX and GND terminals. Keep cable runs
between the device and the dry contacts under two metres. The function of the Auxiliary input will need to be programmed
at the time of commissioning.
product specifications
Control Supply:
Load Outputs:
Switching Device:
Supply Terminals:
Load Terminals:
IO:
DyNet DC Supply:
Presets:
Programmable Logic:
Compliance:
Ambient Temperature:
Construction:
Dimensions:
Weight:
Dynalite manufactured by WMGD Pty Ltd (ABN 33 097 246 921) Unit 6, 691 Gardeners Road Mascot NSW 2020 Australia Tel: +61 2 8338 9899 Fax: +61 2 8338 9333
230V ±14% 50/60Hz single phase at 0.15A
5 x Feed Thru Outputs at 16A per channel, max total box load is 80A
Wiring topology: 1 Phase & Neutral and 3 Phase & Neutral Star. Delta not supported
5 x Open protocol, each selectable to DALI address, DALI Broadcast, 1-10V or DSI
Relay – 50A 230V AC resistive (5000W Lighting Load rated)
1 x Phase, 1 x Neutral 1 x Earth, up to 1 x 4mm
IN, OUT for each channel, up to 1 x 4mm
1 x RS485 DyNet serial port
1 x AUX programmable dry contact input
200mA (capacity for approx 5 Panels)
170
8 Tasks, most UPAN mnemonics supported
CE, C-Tick
50C max.
Polycarbonate plastic DIN rail mount
Height 93mm x Width 211mm x Depth 75mm
0.8Kg
DDBC516FR-DALI Rev B Specifications subject to change without notice