Download Print this page
Philips dynalite DALI DDBC120-DALI User Manual

Philips dynalite DALI DDBC120-DALI User Manual

Multi master controller

Advertisement

Quick Links

DDBC120-DALI
DALI Multi Master Controller
To reduce the risk of fire or electric shock, do not expose this device to rain or moisture. Installation, programming and maintenance must be
carried out by qualified personnel. All local wiring and electrical regulations must be followed when installing device.
Overview
Single-phase supply – 100 - 240 VAC 50 / 60 Hz at 0.25 A
1 x DALI Output – Suitable for DALI HF ballasts, electronic
low-voltage transformers and LED fixtures. Philips Dynalite multi
master enabled for use with DPMI940-DALI and DUS360CR-
DALI only.
1 x Feed-through Switched Circuit – Rated at 20 A
Built-in DALI Bus Power Supply of 220 mA @ 16 VDC –
Auto restart on overload or short circuit on DALI output. No
external DALI power supply allowed.
Override and Status Indicator for Switched Channel
Many Control Options – Control of this device can be via
a combination of methods, such as serial control port, relay
contacts, push button control panels, infrared receivers,
timeclocks and Philips Dynalite user interfaces on the DALI
network.
Dry Contact Interface – Can be programmed to perform many
different functions. The factory settings will cause this input to
transmit network identification information.
Simple Installation – DIN rail mount facilitates installation. All
connection terminals accessible without disassembly.
Electrical Diagram
µP
Shield
GND
D +
D -
+VE
AUX
DyNet
RS485
RJ12
WARNING:
Do not connect any DALI terminals or wires to mains power. DALI wires are NOT
SELV and should never be considered touch safe. Basic insulation or higher is required between
DALI wires and mains cabling.
Do not connect external DALI power supply to the same DALI bus.
Warning – Read the instructions - We recommend that you read
this instruction manual prior to commencement of installation.
Standards - The temperature limits and carrying capacity of
communication wires must comply with HD 384.5.523 and the
installation of home and building automation and control systems
must comply with HD 60364-4-41.
Special Programming – This device is designed for professional
installation only, and will only operate in basic modes unless
programmed via a computer. If programming is required, contact
your local agent for details. Once the data cable is connected to
the devices, the factory default settings will allow any control panel
to control all channels in all dimmers.
Check Connections – Re-tighten all connections after installation.
Power Sources – This device should only be operated from the
type of supply specified on the front cover. This device must be
earthed.
Output Circuit – The load on the switched circuits should not
exceed the specified capacity of 20 A, these circuits should be fed
via a 20A circuit breaker.
Supply:
Load Control Circuit – A 2 core DALI bus cable is required to be
E
100-240V 0.25A
run to the loads. This cable is in addition to the mains feed.
N
50/60Hz
L
Single Phase
Load Type – This product is intended to control DALI drivers and
devices.
IN
LOOP
Location – Install in a dry, well-ventilated location. Controllers may
OUT
emit some mechanical noise. Take this into account when deciding
the mounting location.
IN
RELAY
OUT
Data Cable – Use screened, stranded RS485 data cable with three
twisted pairs. Segregate from mains cable by 300mm minimum.
Connect devices in a 'daisy chain'. A data cable connected to an
energized device is live. Do not cut or terminate live data cables.
DA-
DALI
DA+

Advertisement

loading

Summary of Contents for Philips dynalite DALI DDBC120-DALI

  • Page 1 Once the data cable is connected to timeclocks and Philips Dynalite user interfaces on the DALI the devices, the factory default settings will allow any control panel network.
  • Page 2 The DALI bus is not SELV and must be treated as a mains cable. DALI is not polarity conscious. A maximum of 64 DALI devices plus 10 Philips Dynalite user interface devices (DPMI940-DALI & DUS360CR-DALI) can be connected together in a DALI network.