Intended use

CE marking and ATEX approval

Regard-1 is CE marked to indicate conformity to the following directives:
"ATEX directive" 94/9/EC
"EMC directive" 89/336/EEC
"Low-voltage directive" 73/23/EEC
The control unit also bears the following ATEX marking:
WARNING!
THIS MARKING DOES NOT MEAN THAT THE UNIT IS "EXPLOSION
PROOF".
Regard-1 cannot be used in areas subject to explosion hazards
("hazardous areas") without suitable protection.

Other tests and approvals

In addition to the measuring function for flammable gases in the range 0 to 100 %LEL
and for oxygen (inertisation) in the range 0 to 25 %(V/V), Regard-1 has been tested
according to DIN EN 45544-1 combined with DIN EN 45544-2 for toxic gases, and
according to DIN EN 50104 for oxygen enrichment and oxygen deficiency, by EXAM
BBG Prüf- und Zertifizier GmbH, Dinnendahlstrasse 9, 44809 Bochum, Germany.
The "Bericht über die Eignungsuntersuchung" has been issued under PFG-No.
41301303.
In Germany only:
NOTE
Read and consider chapter 5 of the "Bericht über die
Eignungsuntersuchung".
Issue 5 - June 2005
II (2) G
Page 10 of 64 Pages