3.1 Connect Input Power to Energy Pack

Before connecting input power, see complete
installation instructions in the PACSystems
Controllers: Battery and Energy Pack Manual,
GFK-2741E or later.
You will need:
A 24Vdc, 72W SELV power supply
A power cord with 18 AWG (0.82mm
An 18 AWG (0.82mm
An input power terminal block – provided
(Weidmuller part number 1748010000)
A small flat-head screwdriver (such as a 1.4mm
jeweler's screwdriver)
Using the power cord, connect the power supply
1.
output to the Energy Pack's input power terminal
block.
To insert the wires in the power terminal block
connector, you may need to use the small
screwdriver to release the spring clamp on the
terminal block.
Recommended wire stripping length is
7mm (0.28 in).