Error code display and actions
The error codes are viewed on the display screen. After the error codes are displayed, the sys-
tem is shut off for 60 sec. and re-started (except for ba11). If the same error occurs more than
6 times within 60 minutes, the A/C system will be completely stopped. In this case, it can only
start again if the error has been solved and the system has been completely switched off and
on again.
Error codes and causes
AAA
A01
A02
A03
A04
A05
A06
A07
A08
A09
A10
CA11
bA11
Persistent low voltage (below limit for more than 5 sec. See Installation
Instructions for further details.)
Low pressure cut-out compressor 1
COOL mode: Insufficient chilled water flow.
HEAT mode: Insufficient seawater flow or seawater temperature in
heat mode too low (< 7 °C), heat mode not possible.
High pressure cut-out compressor 1
COOL mode: Insufficient seawater flow.
HEAT mode: Insufficient chilled water flow.
Low pressure cut-out compressor 2 (causes see A01)
High pressure cut-out compressor 2 (causes see A02)
Low pressure cut-out compressor 3 (causes see A01)
High pressure cut-out compressor 3 (causes see A02)
Low pressure cut-out compressor 4 (causes see A01)
High pressure cut-out compressor 4 (causes see A02)
Room temperature sensor defective or absent.
Temperature sensor at chilled water loop defective or absent.
All compressors have been deactivated. Re-activate with the
No error but status information, indicating that blower is in standby
mode. Blower will automatically start once chilled water circuit has
reached required temperature.
code
menu