GE PACSystems RX3i User Manual page 9

Power sync and measurement system
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

RX3i Power Sync and Measurement System
%I Bit
Definition
Offset
56
GRID 1 OverVoltAlarm
57
GRID 1 VIImbalanceAlarm
58
GRID 1 UnderFreqAlarm
59
GRID 1 OverFreqAlarm
60 - 64
Reserved
65
GRID 2 ClampedFreq:
66
GRID 2 ClampedInput:
67
GRID 2 MixedPolarity
68
GRID 2 VoltPhSeqAlarm
69
GRID 2 UnderVoltAlarm
70
GRID 2 ReversPwrAlarm
71
GRID 2 OverCurrAlarm
72
GRID 2 OverVoltAlarm
73
GRID 2 VIImbalanceAlarm
74
GRID 2 UnderFreqAlarm
75
GRID 2 OverFreqAlarm
76 – 80
Reserved
Status/Alarm Timing
Timing A – The PSM buffers an entire power line cycle and takes 11 ms to perform calculations on the waveforms. The new
status bits are available to the application code after the next PLC input data scan.
Total latency = 1-cycle + 11 ms + (0 to PLC scan time)
Update rate = 1-cycle or the PLC scan rate (whichever is longer)
Timing B – The PSM updates this information every 100 ms. The new status bits are available to the application code after
the next PLC input data scan.
Value
0 = OK
1 = ANSI 59 Alarm
0 = OK
1 = ANSI 60 Alarm
0 = OK
1 = ANSI 81U Alarm
0 = OK
1 = ANSI 81O Alarm
0 = OK
1 = Line Frequency outside the
range (30 - 70 Hz)
0 = OK
1 = some inputs have signal
clamped
0 = OK
1 = At least one phase PT/CT has
wrong polarity
0 = OK
1 = ANSI 47 Alarm
0 = OK
1 = ANSI 27 Alarm
0 = OK
1 = ANSI 32 Alarm
0 = OK
1 = ANSI 50 Alarm
0 = OK
1 = ANSI 59 Alarm
0 = OK
1 = ANSI 60 Alarm
0 = OK
1 = ANSI 81U Alarm
0 = OK
1 = ANSI 81O Alarm
Status/Alarm
Alarm
Timing
Availability
A, B, AB: Refer to
the section,
ø
1
Status/Alarm
Timing
B
B
B
ü
B
ü
A
ü
A
ü
B
B
B
B
B
ü
B
B
B
ü
B
ü
9
GFK-2748C
2
ø
3
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü