12
GFK-2748C

Release History

Version
IC694PSM001-AB
IC694PSM001-AA
Important Product Information for Release 1.01

New Features and Enhancements

With this release, the PSM accounts for the breaker delay, and the rate of change of the phase shift between the grids, to time
the CloseRelayOK status and ACC200 relay outputs to close the sync relay contacts when the phase shift between the grids is
0⁰.
This release also adds the special case of Breaker Delay = 0. When the ANSI 25 Breaker Delay parameter is set to 0, the
PSM turns off breaker delay calculations and operates in Classic sync relay mode. In Classic mode, the PSM sets the
CloseRelayOK status and the ACC200 relay outputs to On whenever the application requests a sync and the phase shift
between the grids is in the range –Phase Shift Threshold to +Phase Shift Threshold.
Functional Compatibility
Subject
Programmer Version
Requirements
CPU Firmware Version

Operational Notes

Subject
Wiring
Firmware
Revision
1.01
January 2013
1.00
December 2012
Proficy Machine Edition Logic Developer 7.50 with SIM 2 or newer or
Proficy Machine Edition Logic Developer 7.00 with SIM 12 or newer or
Proficy Machine Edition Logic Developer 7.60 or newer
RX3i CPU firmware versions 7.15, 7.16, 7.17, and 7.18.
Note:
The PSM module is not compatible with IC695CPE305 and C695CPE310
firmware version 7.30.
CPU firmware version 7.70 or newer support the IC694PSM001 module on these
CPU types:
IC695CPE305
IC695CPE310
IC695CPU315
IC695CPU320
IC695CRU320, including –QP (Quad Redundancy)
IC695NIU001+
COM1 and COM2 of the IC694ACC200 must be connected to functional ground
(Earth ground).
COM1 and COM2 must not be connected to Neutral in a WYE power system.
In certain fault conditions, Neutral can be pulled to the full voltage of any phase. Such
a fault condition can pose a danger to personnel and damage the IC694ACC200. See
GFK-2749 for wiring diagrams.
RX3i Power Sync and Measurement System
Date
Enhanced operation of sync relay feature as
described below.
Initial release
Version Required
Description
Comments