Step 7
Connection Wiring
Loop cables should only be passed via the access points
available.
Flame retardant cable glands must be used.
Cable lengths should be kept to a minimum to ensure cables are
away from the PCBs aerials.
Single Loop Module
Control
Panel
Screen
Loop
+
Out
-
+
Loop
In
-
Screen Not Connected
Multiple Loop Modules (max 5)
Loop Module 1
Loop
Loop
In
Out
+ -
+ -
Control
Panel
Screen
Loop
+
Out
-
+
Loop
In
-
Screen Not Connected
Step 9
Applying Power
Apply power to the Control Panel. The normal LED states for the
Loop Module are as below:
Healthy LED - Green LED will be on.
Fault LED - Yellow LED will be off.
Sys Fault LED - Yellow LED will be off.
POWER
FAULT
ISOLATE
Specification
Operating
Temperature
-10°C to 50°C (ambient)
Storage
Temperature
0°C to 35°C
LOOP 1
LOOP 2
IN OUT IN OUT
IN OUT IN OUT
-
-
-
Humidity
Up to 95% non-condensing
Operating
Voltage
17 to 28V DC
Power
Requirements
17mA @24V DC
IP Rating
IP54
Operating
Frequency
868MHz
Output
Transmitter
Power
Variable 0 - 14 dBm
Dimensions
270mm (W) 205mm (H) 75mm (D)
Weight
0.95kg
Location
Type A: For indoor use
Regulatory Information
Manufacturer
EMS. Technology House, Herne Bay, Kent, CT6 8JZ, United Kingdom
Year of
manufacture
See devices serial number label
©2014 EMS Radio Fire & Security Systems Ltd. All rights reserved
Loop Module 1
Loop Module 2
Loop Module 3
Loop
Loop
In
Out
+ -
+ -
RF1
RADIO
TX
RX
RESET
POWER
FAULT
ISOLATE
WD
LOOP IN
LOOP OUT
-
-
-
Step 8
The address number is set using the onboard 8 way switch.
Available selections are shown in the table below.
DIL
switch
setting
addr
1..........8 addr
1
10000000 11
2
01000000 12
3
11000000 13
Loop
Loop
4
00100000 14
In
Out
5
10100000 15
+ -
+ -
6
01100000 16
7
11100000 17
8
00010000 18
9
10010000 19
10
01010000 20
51
11001100 61
52
00101100 62
53
10101100 63
54
01101100 64
55
11101100 65
56
00011100 66
57
10011100 67
58
01011100 68
Loop
Loop
59
11011100 69
In
Out
60
00111100 70
+ -
+ -
101 10100110 106 01010110 111 11110110 116 00101110 121 10011110
102 01100110 107 11010110 112 00001110 117 10101110 122 01011110
103 11100110 108 00110110 113 10001110 118 01101110 123 11011110
104 00010110 109 10110110 114 01001110 119 11101110 124 00111110
105 10010110 110 01110110 115 11001110 120 00011110 125 10111110
The Loop Modules programming is configured using the Loop
Modules menu structure.
Refer to the Engineers Guide (Doc Ref: TSD062) for full
programming details.
RF2
Step 10
Ensure that the Loop Module PCB is correctly inserted and the
PCB retaining screw is refitted.
Refit the Loop Module lid, ensuring all four lid screws and
corner covers are fitted.
Care must be taken to ensure the LEDs are not damaged by
the light pipe when refitting the Loop Module Lid.
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7
0V
RX
HELP
TX
3V
BACK
Certification
Certification
body
CPR Certificate
Approved to
European Union
directives
Contact Information
EMS General
2/2
Configuration
DIL
DIL
switch
switch
setting
setting
1..........8 addr
1..........8 addr
11010000 21
10101000 31
00110000 22
01101000 32
10110000 23
11101000 33
01110000 24
00011000 34
11110000 25
10011000 35
00001000 26
01011000 36
10001000 27
11011000 37
01001000 28
00111000 38
11001000 29
10111000 39
00101000 30
01111000 40
10111100 71
11100010 81
01111100 72
00010010 82
11111100 73
10010010 83
00000010 74
01010010 84
10000010 75
11010010 85
01000010 76
00110010 86
11000010 77
10110010 87
00100010 78
01110010 88
10100010 79
11110010 89
01100010 80
00001010 90
Reassemble the Loop Module
RX
F usion
POWER
FAULT
Loop Module
ISOLATOR
ACTIVE
0359
0359-CPR-0222
EN54-17:2005
EN54-18:2005
EN54-25:2008
1999/5/EC (R&TTE directive):
Hereby EMS Radio Fire & Security Systems declares that this device is in
compliance with the essential requirements and other relevant provisions
of Directive 1999/5/EC.
2002/96/EC (WEEE directive):
Products marked with this symbol cannot be disposed of as unsorted
municipal waste in the European Union. For proper recycling, return this
product to your local supplier upon purchase of equivalent new
equipment, or dispose of it at designated collection points. For more
information see www.recyclethis.info
EMS. Technology House, Herne Bay, Kent, CT6 8JZ, United Kingdom
t: +44 (0) 1227 369570
f: +44 (0) 1227 369679
e: enquiries@emsgroup.co.uk
www.emsgroup.co.uk
DIL
DIL
switch
switch
setting
setting
1..........8 addr
1..........8
11111000 41
10010100
00000100 42
01010100
10000100 43
11010100
01000100 44
00110100
11000100 45
10110100
00100100 46
01110100
10100100 47
11110100
01100100 48
00001100
11100100 49
10001100
00010100 50
01001100
10001010 91
11011010
01001010 92
00111010
11001010 93
10111010
00101010 94
01111010
10101010 95
11111010
01101010 96
00000110
11101010 97
10000110
00011010 98
01000110
10011010 99
11000110
01011010 100 00100110
126 01111110
TSD077 Iss 3c 15/04/14
AJM

Advertisement

loading

This manual is also suitable for:

Fusion fcx-532-002