Universal Controller - 3 Range
ZA-10065-EET
Issue a : 14/5/97
Commissioning:
2. Make sure that the controller software is EET.
3. Check / Set Bit Switches (Fig. 1).
4. Switch the controller ON.
5. Connect Set-up Unit to DIN Box Display or
controller (Fig. 2).
6. Check / Set operating parameters - see list
7. Save values - if changed
8. Log the controller on to the network then verify
settings on Genus InTouch panel, Set-up Unit
or DIN Box Display.
9. Faults ?..........See 'Fault Finding'.
Fault Finding:
Set-up Unit does not reach the first
screen.
If the red LED beside the display connector is
ON, then the controller is faulty.
You cannot log the controller on to the
network.
There may be a controller with the same name,
already logged on the network.
There may be a maximum 32 controllers
already on the network segment.
Check on the InTouch panel, P.C. or
Supervisor.
Display Alarm Messages:
AL
Temperature alarm
Ft
Probes 1 and 2 are faulty
LA
Log probe alarm
Pn
probe 'n' faulty or not connected
(Where 'n' = pro be number)
EE
EEPROM fault
rr
Internal program fault
En
Plant fault ('n' = number)
Comments:
Store:..................................................
Controller
Name:
Designer:.............................................
Date:...................................................
Engineer:.............................................
Date:...................................................
Parameter
Red Cycle Temperature
Red OT Alarm Temp.
Red UT Alarm Temp.
Yellow Cycle Temperature
Yellow OT Alarm Temp.
Yellow UT Alarm Temp.
White Cycle Temperature
White OT Alarm Temp.
White UT Alarm Temp.
Case Type: 0=Red ; 1=Yellow
; 2=White
Alarm Delay
Log Probe Type: 0=Off ;
1=Product ; 2=Alarm ;
3=Prod./Alarm
Red Log OT Alarm
Red Log UT Alarm
Yellow Log OT Alarm
Yellow Log UT Alarm
White Log OT Alarm
White Log UT Alarm
Defrost Start
Number of Defrosts per Day
Gas Defrost Detect
Temperature
Defrost Minimum Time
Drain Down Time
Defrost Recovery Time
Defrost Type: 0=Elect.;
1= 2Gas ; 2= 3Gas
Defrost Mode: 0=Local ;
1=Remote
Defrost Hold: 0=Off ; 1=On
Fans in Defrost: 0=Off ; 1=On
Hour
Minute
Day
Month
Year
BST / GMT Select: 0=Auto ;
1=Man.Off ; 2=Man.On
Lights / Blind: 0=Local ;
1=Remote ; 2=Man.Off ;
3=Man.On
Sunday (Blinds) Up / Down
Monday Up / Down
Tuesday Up / Down
Wednesday Up / Down
Thursday Up / Down
Friday Up / Down
Saturday Up / Down
Superheat reference
Proportional Gain
Integral Gain
Integral Time
EEV Size
Temp. Proportional Gain
Temp. Integral Gain
Temp. Integral Time
Manual Defrost: 0=Off ; 1=On
DIN
Range/Units
0
1 to 7 / °C
2
7 to 10 / °C
1
-3 to 4 / °C
3
1 to 7 / °C
5
7 to 10 / °C
4
-3 to 4 / °C
6
1 to 7 / °C
8
7 to 10 / °C
7
-3 to 4 / °C
9
0 to 30 / °C
10
0 to 2
00:00 to 99:00/Min:Sec
12
0 to 3
14
8 to 10 / °C
13
-1 to 4 / °C
16
5 to 7 / °C
15
-2 to 1 / °C
18
12 to 14 / °C
17
3 to 7 / °C
11
0 to 100 / %
19
00:00 to 23:59/Hrs:Mins
20
0 to 8
21
0 to 25 / Hrs.
22
0 to 30 / °C
23
6 to 14 / °C
24
00:00 to 99:00/Min:Sec
25
00:00 to 99:00/Min:Sec
26
00:00 to 20:00/Min:Sec
27
00:00 to 99:00/Min:Sec
28
0 to 2
29
0 to 1
30
0 to 1
31
0 to 1
32
0 to 23
33
0 to 59
34
0 to 31
35
0 to 12
36
0 to 99
37
0 to 2
38
0 to 3
39/40
00:00 to 23:59/Hrs:Mins
41/42
00:00 to 23:59/Hrs:Mins
43/44
00:00 to 23:59/Hrs:Mins
45/46
00:00 to 23:59/Hrs:Mins
47/48
00:00 to 23:59/Hrs:Mins
49/50
00:00 to 23:59/Hrs:Mins
51/52
00:00 to 23:59/Hrs:Mins
53
54
55
Do not change the
56
value of these
57
parameters
58
59
60
99
0 to 1
Default
Dsgn
Act.
HT(LT)
4 (-22)
8 (-15)
2 (-30)
1 (-22)
5 (-15)
-1 (-30)
8 (-22)
12 (-15)
4 (-30)
1.5 (2)
0
05:00
(10:00)
0
8(-15)
2(-25)
5(-15)
0(-25)
12(-15)
4(-25)
50
01:00
6
7
18
10 (14)
05:00
24:00
(25:00)
01:30
30:00
0
0
0
1
0
0
08:00/20:00
08:00/20:00
08:00/20:00
08:00/20:00
08:00/20:00
08:00/20:00
08:00/20:00
8.0 (6.0)
2.0
2.0
03:00
1.0
1.5
0.7
10:00
0
EEV004y 7B30FE