Universal Controller - F/G Door
ZA-10066-EET
Issue a : 14/5/97
Commissioning:
1. Check all electrical connections (Fig. 2).
2. Make sure that the controller software is EET.
3. Check / Set Bit Switches (Fig. 1).
4. Switch the controller ON.
5. Connect Set-up Unit to DIN Box Display or
controller (Fig. 2).
6. Check / Set operating parameters - see list
7. Save values - if changed
8. Log the controller on to the network then verify
settings on Genus InTouch panel, Set-up Unit
or DIN Box Display.
9. Faults ?..........See 'Fault Finding'.
Fault Finding:
Set-up Unit does not reach the first
screen.
If the red LED beside the display connector is
ON, then the controller is faulty.
You cannot log the controller on to the
network.
There may be a controller with the same name,
already logged on the network.
There may be a maximum 32 controllers
already on the network segment.
Check on the InTouch panel, P.C. or
Supervisor.
Display Alarm Messages:
AL
Temperature alarm
Ft
Probes 1 and 2 are faulty
Pn
probe 'n' faulty or not connected
(Where 'n' = probe number)
EE
EEPROM fault
rr
Internal program fault
En
Plant fault ('n' = number)
Comments:
Store:..................................................
Controller
Name:
Designer:.............................................
Date:...................................................
Engineer:.............................................
Date:...................................................
Parameter
Cut in Temperature
Differential Below

Air On / Off Weight

OT Alarm
UT Alarm
Alarm Delay
Defrost Start
Number of Defrosts per Day
No Defrost Time
Gas Defrost Detect
Defrost Terminate Temperature
Defrost Minimum Time
Defrost Maximum Time
Drain Down Time
Defrost Recovery Time
Defrost Type: 0=Elect.; 1= 2Gas
; 2= 3Gas
Defrost Mode: 0=Local ;
1=Remote
Defrost Hold: 0=Off ; 1=On
Fans in Defrost: 0=Off ; 1=On
Hour
Minute
Day
Month
Year
BST / GMT Select: 0=Auto ;
1=Man.Off ; 2=Man.On
Lights / Blind: 0=Local ;
1=Remote ; 2=Man.Off ;
3=Man.On
Sunday:Lights(Blinds) On (Up)
Sunday:Lights(Blinds) Off(Down)
Monday: On(Up)
Monday: Off(Down)
Tuesday: On(Up)
Tuesday: Off(Down)
Wednesday: On(Up)
Wednesday: Off(Down)
Thursday: On(Up)
Thursday: Off(Down)
Friday: On(Up)
Friday: Off(Down)
Saturday: On(Up)
Saturday: Off(Down)
Superheat reference
Proportional Gain
Integral Gain
Integral Time
EEV Size
Temp. Proportional Gain
Temp. Integral Gain
Temp. Integral Time
Manual Defrost: 0=Off ; 1=On
DIN
Range/Units
0
-49 to 30 / °C
1
0 to 30 / °C
2
0 to 100 / %
4
-49 to 60 / °C
3
-49 to 60 / °C
5
00:00 to 99:00/Min:Sec
6
00:00 to 23:59/Hrs:Mins
7
0 to 8
8
0 to 25 / Hrs.
9
0 to 30 / °C
10
-49 to 30 / °C
11
00:00 to 99:00/Min:Sec
12
00:00 to 99:00/Min:Sec
13
00:00 to 20:00/Min:Sec
14
00:00 to 99:00/Min:Sec
15
0 to 2
16
0 to 1
17
0 to 1
18
0 to 1
19
0 to 23
20
0 to 59
21
0 to 31
22
0 to 12
23
0 to 99
24
0 to 2
25
0 to 3
26
00:00 to 23:59/Hrs:Mins
27
00:00 to 23:59/Hrs:Mins
28
00:00 to 23:59/Hrs:Mins
29
00:00 to 23:59/Hrs:Mins
30
00:00 to 23:59/Hrs:Mins
31
00:00 to 23:59/Hrs:Mins
32
00:00 to 23:59/Hrs:Mins
33
00:00 to 23:59/Hrs:Mins
34
00:00 to 23:59/Hrs:Mins
35
00:00 to 23:59/Hrs:Mins
36
00:00 to 23:59/Hrs:Mins
37
00:00 to 23:59/Hrs:Mins
38
00:00 to 23:59/Hrs:Mins
39
00:00 to 23:59/Hrs:Mins
40
41
42
Do not change the
43
value of these
44
parameters
45
46
47
99
0 to 1
Default
Dsgn
Act.
HT(LT)
0 (-20)
1.5 (2)
50
5 (-16)
-2 (-25)
20:00
01:00
6
7
18
10 (14)
05:00
24:00
(25:00)
01:30
30:00
0
0
0
1
0
0
08:00
20:00
08:00
20:00
08:00
20:00
08:00
20:00
08:00
20:00
08:00
20:00
08:00
20:00
8.0 (6.0)
2.0
2.0
03:00
1.0
1.5
0.7
10:00
0
EET004f 7B30FE