Electrical Installation - Danfoss VLT BACnet/IP MCA 125 Installation Manual

For use with vlt hvac drive fc 102
Table of Contents

Advertisement

Installation

3.7 Electrical Installation

3.7.1 Cabling Requirements
Select cables suitable for Ethernet data
3
3
transmission. Normally, CAT5e and CAT6 cables
are recommended for industrial applications.
Both types are available as unshielded twisted
pair and shielded twisted pair. Shielded cables are
recommended for use in industrial environments
and with frequency converters.
A maximum cable length of 100 m (328 ft) is
allowed between the switches.
Use optical fibers for gapping longer distances
and providing galvanic isolation.
10
®
VLT
BACnet/IP MCA 125
3.7.2 Wiring Procedures
Wiring procedure for enclosure types A1–A3
1.
2.
Illustration 3.10 Wiring for Enclosure Types A1–A3
Danfoss A/S © 05/2016 All rights reserved.
Mount the pre-configured cable wires with the
connectors on the fieldbus option. For A1 and A2
enclosures, mount the supplied strain relief on
top of the frequency converter with 2 screws, as
shown in Illustration 3.10. For cable specifications,
refer to chapter 3.7.1 Cabling Requirements.
Position the cable between the spring loaded
metal clamps to establish mechanical fixation and
electrical contact between the cable and ground.
MG92K102