Mitsubishi Electric QAHV-N560YA-HPB Installation & Operation Manual page 42

Hot water heat pump unit
Hide thumbs Also See for QAHV-N560YA-HPB:
Table of Contents

Advertisement

Usage example
Operation example (Three-sensor method - when a remote controller PAR-W31MAA is used)
Operation mode: Mode 1
Mode 1 Thermo-ON thermistor selection (Item code 1500): 1
Mode 1 Thermo-OFF thermistor selection (Item code 1501): 3
TH15 temperature < (Set water
temperature - Mode 1 Thermo
differential value [Code: 1508])
Unit operation start
* Use the separately sold TW-TH16E temperature thermistor.
Two or more units are needed to use the six-sensor method.
* Make sure to set the unit outlet hot water temperature.
TH15
TH16
Tank
TH17
TH15
TH16
Tank
TH17
TH17 temperature >
Set water temperature
Unit operation stop
42
* Set the operation mode and water
temperature from the remote controller
PAR-W31MAA.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Qahv

Table of Contents