Note:
• Make sure the cables are not coming out of the rubber bushing cut.
Top view
Wiring
Rubber bushing
• When threading the wiring through the rubber bushing, make sure the rubber bushing will not come off the sheet
metal on the control box guard.
Sheet metal on
the guard
Rubber bushing
• When tying the supplied tie band around the rubber bushing, make sure to leave no gap between the ends.
Tie band
Overlapped
Cut on the
rubber bushing
rubber bushing
A power wire exceeding the specified power wire thickness cannot be connected to the power terminal block (TB2).
Use a separate pull box.
To ensure that the transmission cable is not affected by electrical noise from the power cable, route the power cable
away from the transmission cable (distance of at least 50 mm (2 in)).
Wiring
Cut
Rubber bushing
(oval part)
Rubber bushing
(oval part)
Top view
Approx. 20 mm (13/16 in)
There is a gap in
the rubber
bushing.
Cables are coming out of the rubber bushing.
Wiring
Cross-sectional view
Sheet metal on
the guard
Rubber bushing
<<Important>>
When putting the tie band on the rubber bushing, make sure the
ends of the rubber bushing overlap each other as shown in the
figure at left.
Cut on the
rubber
* If there is a gap, water from snow or rain may enter, resulting in
bushing
equipment damage.