<6> Function setting
Function description
Sets the functions for each connected unit from the remote controller as required.
Refer to the Installation Manual for the connected units for details on the connected unit settings at shipment, Function No. and the Data.
If the function settings change the connected unit functions, all the settings must be managed appropriately, such as by writing them down
on paper.
Button operation
1
Unit1
Service
F1
F2
2
Unit1
Password input
Press +/- to set password
F1
F2
3
Unit1
Unit initial set
Check
Contact name
Contact number
Password protection
F1
F2
In the Operation setting screen, press the [F1] button to move the cursor to
FRI
Power Save.
Yes
Press the [F3] button to select "Yes".
No
Normal
No
Next
F3
F4
Select "Service" from the Main menu, and press the [Select] button.
FRI
F3
F4
A password input screen will be displayed.
FRI
Enter the current maintenance password (a 4-digit number).
After entering the 4-digit password, press the [Select] button.
If the password is correct, the Service menu will be displayed.
F3
F4
Select "Unit initial set" from the Service menu, and press the [Select] button.
FRI
F3
F4