Operational data
Environmental
conditions
Norms and standards
General
12/14
Siemens
Building Technologies
Switching differential, adjustable from 0.5..4 K
Heating mode (factory setting)
Cooling mode (factory setting)
Setpoint setting range
Normal operation
Economy (Energy saving) (only with RDF110)
Protection (Standby)
Factory setting of setpoints
Normal operation
Economy (Energy saving) in heating / cooling
mode
Protection (Standby) (heating and cooling mode)
Built-in room temperature sensor
Measuring range
Accuracy at 25 °C
Temperature calibration range
Resolution of settings and display
Setpoints
Current temperature value displayed
Operation
Climatic conditions
Temperature
Humidity
Transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
Storage
Climatic conditions
Temperature
Humidity
EU Conformity (CE)
RCM Conformity
Devices of safety class
Pollution class
Degree of protection of housing
Connection terminals
Weight
Color of housing front
*) The documents can be downloaded from http://siemens.com/bt/download.
Room Temperature Controllers
2 K
1 K
5...40 °C
OFF, 5...40 °C
OFF, 5...40 °C
20 °C
16 °C / 28 °C
OFF
0...49 °C
< ± 0.5 K
± 3.0 K
0.5 °C
0.5 °C
to IEC 60721-3-3
class 3K5
0 ...+ 50 °C
< 95 % r.h.
to IEC 60721-3-2
class 2K3
− 25...+60 °C
< 95 % r.h.
class 2M2
to IEC 60721-3-1
class 1K3
− 25...+60 °C
< 95 % r.h.
*)
CE1T3057xx
*)
CE1T3057en_C1
II to EN 60730-1
normal
IP 30 to EN 60 529
solid wires or prepared
stranded wires
2
2 x 0.4-1.5 mm
or 1 x 2.5
2
mm
0.28 kg
white, NCS S 0502-G
(RAL 9003)
N3057en
2014-10-28