ITC 450/470
User manual
Parameter
CHAr
Conversion characteristic mode
Pnt
Decimal point position
Lo C
Minimum displayed value (for nominal range)
Hi C
Maximum displayed value (for nominal range)
Lo r
Extension of the bottom of the nominal input range
Hi r
Extension of the top of the nominal input range
Omod
Active current output mode
OUtL
Display value for 0 mA or 4 mA current output
OUtH
Display value for 20 mA current output
Lo r
Extension of the bottom of the nominal output range
Hi r
Extension of the top of the nominal output range
AL
Current output value on critical exception
Omod
Passive current output mode
OUtL
Display value for 4 mA current output
OUtH
Display value for 20 mA current output
Lo r
Extension of the bottom of the nominal output range
Hi r
Extension of the top of the nominal output range
AL
Current output value on critical exception
Omod
Active voltage output mode
OUtL
Display value for 0 V, 1 V or 2 V voltage output
OUtH
Display value for 5 V or 10 V voltage output
Description
Active current output configuration ("OUtP" menu)
Passive current output configuration ("OUtP" menu)
Active voltage output configuration ("OUtP" menu)
Default
User's
Value
Value
Lin
0.0
000.0
100.0
5.0 (%)
5.0 (%)
„0-20" (mA)
0.0
100.0
5.0 (%)
5.0 (%)
22.1 (mA)
„4-20" (mA)
0.0
100.0
5.0 (%)
5.0 (%)
22.1 (mA)
„0-10" (V)
0.0
100.0
www. levelprosales.com
Desc.
Page
31
31
31
31
32
32
33
34
34
34
34
35
33
34
34
34
34
35
33
34
34
55
Need help?
Do you have a question about the ITC 450 and is the answer not in the manual?