If tA ,tB ,tC or tD (when input signal stay in zone A or zone B) are lower than parameters "t on" or "toFF", the
relay will not change his state (see points A and C, Figure 6.7 a, d, e).
The state of relay output while the input value exceeds the border values (points A, B, C, D) is described by
parameter "modE". The relay can be turned on ("modE" = "on"), or turned off ("modE" = "oFF") when input
signal value is contained in zone A (Figure 6.7 a).
The parameter "AL" allow user to set the relay output behaviour in critical situations (e.g. Input values
exceeds permissible measurement range). User can select that the relays will be turned on, turned off,or not
changed in critical situations.
All parameters connected with relay outputs are described in paragraph "rEL1" menu.

6.3.2. Two thresholds mode

relay state
(modE = in
t on = 0
t oFF = 0)
relay state
(modE = out
t on = 0
t oFF = 0)
relay state
(modE = in
t on = 0
t oFF = 0)
relay state
(modE = out
t on = 0
t oFF = 0)
Description:
A, B, C, D
- points where measured signal exceeds border values (expected value ± allowed deviation)
B
,B
,C
C
E
ON
OFF
ON ,
OFF ,
ON
t
, t
, t
, t
, t
A
B
C
D
E
Figure 6.8. Principle of LED/relay output operation for two thresholds mode
A
B
B
ON
B
OFF
A
B
"t on" parameter
"t oFF" parameter
- relays state changes moments: (for "t on" > 0, "t oFF" > 0)
, E
OFF
- time periods while input signal is in zone A or zone B
C
C
C
OFF
ON
C
"t oFF" parameter
"t on" parameter
"t on" parameter
"t oFF" parameter
E
"HYSt" parameter
E
"SEt P" or "SEt P2"
E
OFF
E
parameter
ON
"HYSt" parameter
www. levelprosales.com