5.6.11 Save or Cancel

At the end of each parameter setting, select "Save"
or "Cancel" by the external adjustment screw
and press the push button to save or cancel the
configuration.
Save or Cancel
Save?
After
parameter
screw
setting
Cancel?
5.6.12 Abort Configuration
5.6.12.1 Abort Configuration (Menu)
Hold down the push button for over 2 seconds to
exit the Local Parameter Setting mode.
Process Measurement Display
1. Tag Number
2. Press Unit
3. Press LRV
4. Press URV
5. Damping Time
6. Output Mode
7. Display Out1
8. LRV-Apply Press
9. URV-Apply Press
Process Measurement Display
5.6.12.2 Abort Configuration (Parameter)
To exit the configuration while editing the value,
hold down the button for over 2 seconds and select
"Save" or "Cancel".
Saved
push

5.6.13 Local Parameter Setting Lock

To disable parameter changes by the Local
Parameter Setting there are three different ways.
Canceled
Communication Parameter
Ext SW =disable
push
(EXT ZERO ADJ = disable)
Communication Parameter
F0521.ai
Write Protect = On
(WRT PROTECT = Yes)
Hardware write protection
switch on CPU assembly =
D (Disable)
*External Zero Adjustment is unlocked.
The above parameter setting is carried out by
using field communicator or DTM. See the user's
manual IM 01C25T (HART/BRAIN) for the setting
procedure.
Reviewing local parameter setting by push button
on the integral indicator is available at any time
even when the Local Parameter Setting is locked.

5.6.14 Others

Hold down the button
for over 2 seconds
Tag Number
Output Mode
(Linear/Sq root)
Proccess Value
F0522.ai
<5. Operation>
Tag editing
(3
Character)
rd
Push for
Over 2 seconds
• Difference between BRAIN and HART
HART
Up to 8
characters can
be set
"TRNS.FC"
shown on the
integral indicator
• The degree of adjustment depends on the
speed of turning the adjustment screw. Turn the
screw slowly for fine tuning and turn the screw
fast for quick tuning.
5-13
Return to
parameter review window
Save or Cancel?
F0523.ai
Locked features
• External Zero
Adjustment
• Local Parameter Setting
• Local Parameter Setting
• All Communication
Parameters *
• Local Parameter Setting
• All Communication
Parameters *
BRAIN
Up to 16
characters can
be set
"OUT.MOD"
shown on the
integral indicator
IM 01C25W01-01EN