Advertisement

5.6.1 Local Parameter Setting (LPS) Overview

Parameter configuration by the external adjustment screw and push button (integral indicator code E) offers
easy and quick setup for parameters of Tag number, Unit, LRV, URV, Damping,Output mode (linear/square
root), Display out 1, and Re-range by applying actual pressure (LRV/URV). There is no effect on measurement
signal (analog output or communication signal) when Local Parameter Setting is carried out.
Figure 5.10 External Adjustment Screw
Measurement
push
1. Tag Number
2. Press Unit
push
3. Press LRV
4. Press URV
push
5. Damping Time
6. Output Mode
push
7. Display Out1
8. LRV-Apply Press
push
9. URV-Apply Press
10. Device Information
Measurement
*: Note that the above 1 to 7 parameter configurations are available with the software revision (SOFT REV)2.03 or later.
Software revision can be checked via a field communicator (HART/BRAIN) or DTM. Please refer to IM 01C25T01 for HART
parameter "Software rev" and IM 01C25T03 for BRAIN "SOFT REV".
Figure 5.12
External adjustment
screw cover
F0513.ai
Process
Display
Activate LPS mode
*
*
*
*
*
*
*
Process
Display
Push-button
Figure 5.11 Range –Setting Switch (push button)
screw
Zero adjustment
Edit Tag number
Select Press unit
Edit Press LRV
Edit Press URV
Edit Damping time
Select Output mode
Edit Display Out1
Set LRV
Set URV
8, 9 : Re-range by applying actual pressure
<5. Operation>
Integral indicator
push
Save/Cancel the value
Save/Cancel the value
Save/Cancel the value
Save/Cancel the value
Save/Cancel the value
Save/Cancel the value
Save/Cancel the value
Save/Cancel the value
Save/Cancel the value
F0515.ai
IM 01C25W01-01EN
5-9
F0514.ai