Selecting Fan Relay Latching Option - "Frl; Selecting Trouble Fan Setting Option - "Tfs; Selecting 4-20Ma Output Option - "420; Onboard Diagnostics - Macurco CD-6MC User Instructions

Carbon dioxide detector, controller and transducer
Hide thumbs Also See for CD-6MC:
Table of Contents

Advertisement

3.5.10 Selecting Fan Relay Latching Option – "FrL"
To select the Fan Relay Latching Option, in normal mode, push the Next button to get to "Con" or the Configuration menu. Then push
the Enter button to enter the Con menu. The tenth selection is the "FrL" or Fan Relay Latching Option. Push Next nine times to get to
"FrL" then Enter. If latching is "OFF" push Next to turn it to "ON" (flashing) then push Enter to confirm the change (solid) and push
Enter again to return to "FrL" in the Con menu. Push Next until "End" is displayed then push Enter to get back to normal operation.
3.5.11 Selecting Trouble Fan Setting Option – "tFS"
To select the Trouble Fan Setting Option, in normal mode, push the Next button to get to "Con" or the Configuration menu. Then
push the Enter button to enter the Con menu. The eleventh selection is the "tFS" or Trouble Fan Setting Option. Push Next ten times
to get to "tFS" then Enter. If Trouble Fan Setting is "OFF" push Next to turn it to "ON" (flashing) then push Enter to confirm the change
(solid) and push Enter again to return to "tFS" in the Con menu. Push Next until "End" is displayed then push Enter to get back to
normal operation.
3.5.12 Selecting 4-20mA Output Option – "420"
To select the 4-20mA Output Option, in normal mode, push the Next button to get to "Con" or the Configuration menu. Then push the
Enter button to enter the Con menu. The twelfth selection is the "420" or 4-20mA Output Option. Push Next eleven times to get to
"420" then Enter. If the 4-20mA is "On" push Next to turn it to "OFF" (flashing) then push Enter to confirm the change (solid) and push
Enter again to return to "420" in the Con menu. Push Next until "End" is displayed then push Enter to get back to normal operation.

3.6 Onboard Diagnostics

The CD-6"x" monitors all critical functions of the unit through software diagnostics that continuously test and verify unit operations. If a
problem is found, the unit will switch to a fail-safe/error mode or trouble condition. In this error mode, the Alarm relay will be activated,
the 4-20 mA current loop will go to 24 mA, the unit will display the error code, the green status indicator LED light will flash and the
buzzer will chirp intermittently. The Fan relay will also engage if the Trouble Fan Setting Option is set to "ON". This is a safety
precaution. To clear this mode, simply turn off power to the unit for a few seconds or push the ENTER/TEST switch (inside the unit).
This will cause the unit to restart the 1-minute self-test cycle.
3.6.1

The 4-20 mA signal can be used for troubleshooting:

 0 mA is most likely a connection problem
 4-20 mA is normal gas reading range (0-5000 ppm)
 24 mA indicates a Trouble condition
3.6.2

Error Codes

 t001 - Trouble with sensor signal
 t002 - Temperature compensation failed
 t004 - EEPROM bad checksum
 t008 - IR lamp trouble
 t010 - Bad EEPROM
 t020 - Bad calibration
 t040 - Factory calibration failure
 t080 - ADC trouble
 t100 - Under range
 t200 - Sensor expired
 t400 - Pressure sensor trouble
 t800 - PCBA not tested
If the error mode repeats frequently, check for continuous power and proper voltage. If power is not the problem and a unit has
repeating error conditions, it may need to be returned to Macurco for service, per these User Instructions.
If the error mode indicates "Sensor expired" see section
4.1 End-of-life Signal
of these User Instructions.
15

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cd-6h

Table of Contents