Troubleshooting
Fault display
Fault code
System character-
displayed
istics
10
Continuous opera-
tion
18
Continuous opera-
tion
30
Burner blocked
38
Burner blocked
50
No DHW heating
58
No DHW heating
60
Burner blocked
68
Burner blocked
A9
Control mode with-
out OpenTherm de-
vice
b0
Burner blocked
b8
Burner blocked
E5
Burner blocked
F0
Burner blocked
38
(cont.)
Cause
Short circuit, out-
side temperature
sensor
Lead break, out-
side temperature
sensor
Short circuit, boiler
water temperature
sensor
Lead break, boiler
water temperature
sensor
Cylinder demand
terminal box fault
Cylinder demand
terminal box fault
Short circuit, re-
turn temperature
sensor
Lead break, return
temperature sen-
sor
Communication
error, OpenTherm
device
Short circuit, flue
gas temperature
sensor
Lead break, flue
gas temperature
sensor
Internal fault
Internal fault
Measures
Check the outside tem-
perature sensor and lead
(see page 43).
Check the outside tem-
perature sensor and lead
(see page 43).
Check the boiler water
temperature sensor (see
page 44).
Check the boiler water
temperature sensor (see
page 44).
Check terminal box con-
nections and replace the
terminal box if required.
Check terminal box con-
nections and replace the
terminal box if required.
Check the return temper-
ature sensor (see
page 44).
Check the return temper-
ature sensor (see
page 44).
Check connections and
lead; replace OpenTherm
device if required.
Check sensor (see
page 46).
Check sensor (see
page 46).
Check the ionisation
electrode and connecting
cables.
Press "Reset" (see
page 41).
Replace control unit.