Installation sequence
Mounting the boiler and making connections
Gas connection
A
14
(cont.)
1. Connect the gas shut-off valve to
connection A.
2. Carry out a tightness test.
Note
Only use suitable and approved
leak detection agents (EN 14291)
and devices for the tightness test.
Leak detection agents with unsuita-
ble constituents (e.g. nitrides, sul-
phides) can cause material dam-
age.
Remove leak detection agent resi-
dues after testing.
!
Please note
Excessive test pressure will
damage the boiler and the
gas train.
Max. test pressure
150 mbar. If a higher pres-
sure is required for tightness
tests, disconnect the boiler
and the gas train from the
main supply pipe (undo the
fitting).
3. Purge the gas line.