Commissioning, inspection, maintenance
Further details regarding the individual steps

Checking the condensate drain and cleaning the trap

B A
32
(cont.)
1. Check at trap A that the conden-
sate can drain freely.
2. Place an appropriate drip pan
below trap A.
3. Remove locking cap B and drain
the content of trap A into the drip
pan.
4. Replace locking cap B with gas-
ket.
5. Fill trap A with water. For this,
pour approx. 0.3 l of water into the
combustion chamber.