WIKA TR30 Operating Instructions Manual page 21

Resistance thermometer, compact design
Hide thumbs Also See for TR30:
Table of Contents

Advertisement

Available languages

Available languages

7. Configuration model TR30-W
Diagram for measuring range for model TR30-W
Range of possible upper limits to measuring range in °C
-50
-50 °C
-40 °C
0 °C
+10 °C
+20 °C
+50 °C
Please note:
The measuring range of the thermometer is limited by the application
range of the measuring element, not by the adjustable range of the
transmitter.
without neck tube -50 ... +150 °C (-58 ... +302 °F)
with neck tube -50 ... +250 °C (-58 ... +482 °F)
WIKA operating instructions model TR30
0
+100
+250
Measuring range in °C
minimum
maximum
-50 ... -20
-50 ... +250
-40 ... -20
-40 ... +250
0... 20
0 ... 250
10 ... 30
10 ... 250
20 ... 50
20 ... 250
50 ... 230
50 ... 250