Overview The MGate 5118 is an industrial Ethernet gateway for J1939-to-Modbus RTU/ASCII/TCP, PROFINET and EtherNet/IP network communications. Package Checklist Before installing the MGate 5118, verify that the package contains the following items: • 1 MGate 5118 gateway • Quick installation guide (printed) •...
Page 3
Color Description A communication error occurred (Flashing Modbus TCP Client: only) 1. Received an exception code or framing error (parity error, checksum error) 2. Command timeout (slave device is not responding) 3. TCP connection timeout Modbus TCP Server: 1. Received an invalid function code or framing error (parity error, checksum error) 2.
3. Use an Ethernet cable to connect the MGate to the Modbus, Ethernet/IP or PROFINET device. 4. The MGate 5118 is designed to be attached to a DIN rail or mounted on a wall. For DIN-rail mounting, push down the spring...
Page 5
You can download the User's Manual and DSU (Device Search Utility) from Moxa's website: www.moxa.com. Please refer to the User’s Manual for additional details on using the Device Search Utility. The MGate 5118 also supports login via a web browser. Default IP address: 192.168.127.254 Default account: admin...
CAN bus, use the Ext_CAN_L and Ext_CAN_H as extension pins. Ethernet Port (RJ45) Signal Console Port (RS-232) The MGate 5118 series can use a RJ45 serial port to connect to a PC to configure the device. Signal Power Input and Relay Output Pinouts Shielded...
NOTE In the following section, ATEX and C1D2 certifications will be detailed separately. ATEX Information 1. DEMKO Certificate number: 17 ATEX 1848X IECEx Certificate number: IECEx UL 17.0019X 2. Ambient Temperature Range: 0°C to 60°C (for models without suffix –T) -40°C to 75°C (for models with suffix –T only) 3.
Page 8
WARNING EXPLOSION HAZARD The substitution of any components may impair suitability for Class 1, Division 2. WARNING EXPOSURE TO SOME CHEMICALS MAY DEGRADE THE SEALING PROPERTIES OF MATERIALS USED IN THE FOLLOWING DEVICE: Sealed Relay Device U21. WARNING EXPLOTION HAZARD Indoor use and Pollution degree 2.
Need help?
Do you have a question about the MGate 5118 and is the answer not in the manual?
Questions and answers