8-2-3. Monitor Function of Remote Controller Switch

Calling of sensor temperature display

<Contents>
Each data of the remote controller, indoor unit and outdoor unit can be shown by calling the service
monitor mode from the remote controller.
<Procedure>
1
TEST
CL
Push
+
buttons simultaneously for 4 seconds to
call the service monitor mode.
The service monitor shows up, the master indoor unit No. is
displayed at first and then the temperature CODE No.
displayed.
2
Push temperature set
the CODE No. of data to be monitored.
The CODE No. list is shown below.
CODE No.
Data name
01
Room temperature
(Remote controller)
02
Indoor suction temperature (TA)
03
Indoor heat exchanger (Coil)
temperature (TCJ)
04
Indoor heat exchanger (Coil)
temperature (TC)
∗ 07
Indoor fan revolution frequency
∗ F2
Indoor fan calculated operation time
F3
Filter sign time
Indoor discharge temperature*1
∗ F8
(4-way only)
3
UNIT LOUVER
Push
button to select the indoor unit to be monitored.
Each data of the indoor unit and its outdoor units can be monitored.
4
TEST
Pushing
button to returns to the usual display.
TEMP.
buttons and then change
Unit
°C
°C
°C
°C
rpm
×100h
×1h
°C
The indoor discharge temperature of CODE No. [F8] is the esti-
mated value from TC or TCJ sensor.
Use this value to check discharge temperature at test run.
(A discharge temperature sensor is not provided to this model.)
The data value of each item is not the real time, but value delayed
by a few seconds to ten-odd seconds.
– 49 –
is
FILTER
RESET
2
<Operation procedure>
1
CODE No.
Data name
60
Outdoor heat exchanger (Coil) temperature (TE)
61
Outside temperature (TO)
62
Compressor discharge temperature (TD)
63
Compressor suction temperature (TS)
6A
Operation current (× 1/10)
F1
Compressor calculated operation time
FILE NO. SVM-18042-1
<RBC-AMT32E>
TEMP.
ON / OFF
TIMER SET
FAN
MODE
TIME
SAVE
A A
VENT
L L
TEST
SET
CL
SWING/FIX
UNIT LOUVER
T
4
1
3
2
3
4
Returned to usual display
×100h
Unit
°C
°C
°C
°C
A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents