8-2. Troubleshooting

8-2-1. Outline of judgment

The following method can be done to check whether the problem occurred in indoor or outdoor unit.
The error is indicated by indication lamp on the display of the indoor unit. (sensors of the receiving part)
The indoor unit monitors the operating status of the air conditioner, and the blocked contents of self-diagnosis
are displayed restricted to the following cases if a protective circuit works.
Lamp indication
Operation Timer
Ready
No indication at all
Operation Timer
Ready
Flash
Operation Timer
Ready
Flash
Operation Timer
Ready
Alternate flash
Operation Timer
Ready
Alternate flash
Check code
Power supply OFF or miswiring between receiving unit and indoor unit
E01
Receiving error
E02
Sending error
E03
Communication stop
E08
Duplicated indoor unit No.
E09
Duplicated header units of remote controller
E10
Communication error between CPUs on indoor unit P.C. board
E11
Communication error between Application control kit and indoor unit P.C. board
Wire connection error between indoor units, Indoor power OFF
E18
(Communication stop between indoor master and follower or between main
and sub indoor twin)
Miswiring between indoor unit and outdoor unit or connection erorr
E04
(Communication stop between indoor and outdoor units)
P10
Overflow was detected.
P12
Indoor DC fan error
Outdoor unit discharge temp. sensor error
P03
High pressure protective operation, High pressure SW system
P04
error, Power supply error,
P05
Power supply error
P07
Heat sink overheat error
P15
Gas leak detection
4-way valve inverse error (Indoor or outdoor unit detected)
P19
P20
High pressure protective operation
P22
Outdoor unit fan system error
P26
Short-circuit of compressor drive element
Position detection circuit error
P29
Stopped because of error of other indoor units in a group
P31
(Check codes of E03/L03/L07/L08)
– 47 –
: OFF,
Cause of trouble
Receiving unit
Miswiring or wire connection error
between receiving unit and indoor unit
Protective device of indoor unit worked.
FILE NO. SVM-18042-1
: ON,
: Flash (0.5 sec.)
Setup error
Protective
device of
outdoor unit
worked.
Protective device of outdoor unit
worked.