 Characteristics of hot water module flow rate and pressure loss
The following graph shows the range of flow rates used for the hot water module, and the characteristic pressure
losses. Use this as an aid in the local pump procurement process.
048type
Min.
Water flow rate (L/min)
34
Pressure loss (kPa)
12
35
30
25
20
15
10
5
0
30
33-EN
Rated
Max.
40
46
15
18.5
Available flow range
34 to 46 L/min
Flow rate (Rating): 40 L/min
40
Flow rate (L/min)
– 17 –