6.2

I/O daughter card

The following information provides an outline for the installation and application of
the I/O daughter card within the G4 EX.
The I/O daughter card may already be installed in new units, if configured, or can
be added as an upgrade kit to pre-existing units. The following information will
address the installation for the upgrade kit.

6.2.1 Materials supplied in the upgrade kit

-
-
-
-
-
-
-

6.2.2 I/O daughter card specifications

This card expands the capabilities of the explosion-proof flow computer by adding
an additional 12 points of fixed analog and digital I/O points. Specifications for the
I/O daughter card are as follows:
Analog Points
-
-
Digital Points
-
-

6.2.3 Installation

If the unit is currently operating, data must be collected from the unit and the
configuration files saved prior to beginning this procedure.
Page 24
Do not install the I/O daughter card until told to do so in these
instructions. Installation prior to flashing the unit may cause
some older models units to not boot.
1 each I/O Daughter Card
4 each #6 .25 OD Flat Washer
4 each #6 Flat Washer
4 each 6–32 x .625 ¼ Hex Female Spacer
4 each 6–32 x .75 LG, M-F Standoff
1 each I/O Daughter Card Generic Wiring Diagram
1 each CD-ROM with Specified Flash and Configuration Files
3 each 0-10V (10K ohm impedance) analog inputs
1 each 0-20 mA (SINK mode) analog output
4 each Digital inputs/pulse inputs
4 each Digital outputs (optically-isolated type 1A switches capable of
switching 200 mA of 48 VDC or 40 VAC)