Set Points
The following parameters are remembered during power off (permanent memory), are factory set to the Default value, and can be
adjusted to any value in the Range column.
Unit Level Set Points
All basic unit configuration settings require the unit switch to be off in order to make a change. Modifying the Ground Fault
Protection and Comm Module settings require rebooting the controller in order to apply a change.
Table 18: Set Point Default and Range
Description
Basic Unit Configuration
Compressor Type
Compressor Maximum Speed
Compressor VFD Primary RLA
Input Voltage
Ground Fault Protection Option
Comm Module 1
Comm Module 2
Comm Module 3
Unit Mode and Enabling
Unit Enable
Unit Enable Initial Value
Control source
Available Modes - only changeable when
Unit Switch is off
Staging and Capacity Control
Cool LWT
Ice LWT
Start Up Delta T
Shut Down Delta T
Ice Cycle Delay
Clear Ice Delay
RapidRestore
RapidRestore Maximum Power Off Time
Pump Control
Evaporator Pump Control Configuration
Evaporator Recirculation Time
Evaporator Pump 1 Run Hours
Evaporator Pump 2 Run Hours
Evaporator Pump 1 Starts
Evaporator Pump 2 Starts
Condenser Pump Control Configuration
Condenser Pump 1 Run Hours
Condenser Pump 2 Run Hours
Condenser Pump 1 Starts
Condenser Pump 2 Starts
Power Conservation and Limits
LWT Reset Enable
Maximum Reset
Demand Limit Enable
www.DaikinApplied.com
Default
Range
Not Set
Not Set, F3AL, F3BL, F4AL
51 Hz
51 to 78 Hz - dependant on compressor type
100
1 to 1000 amps
Not Set
Not Set, 380, 400, 460, 575
No
No, Yes
None
None, IP, LON, MSTP, Modbus
None
None, IP, LON, MSTP, Modbus
None
None, IP, LON, MSTP, Modbus
Enable
Disable, Enable
Enable
Disable, Enable
Local
Local, Network
Cool
Cool, Cool w/Glycol, Cool/Ice w/Glycol, Ice w/Glycol, Test
44.6°F (7°C)
See below
24.8°F (-4°C)
7.6 to 39.2°F (-8 to 4°C)
4.9°F (2.7°C)
3 to 9°F (1.66 to 5°C)
2.7°F (1.5°C)
1.8 to 3.6°F (1 to 2°C)
12
1-23 hours
No
No, Yes
Disable
Disable, Enable
15 seconds
15 to 180 seconds
#1 Only
#1 Only, #2 Only, Auto, #1 Primary, #2 Primary
30
0 to 300 seconds
0
0 to 999999 hours
0
0 to 999999 hours
0
0 to 999999 starts
0
0 to 999999 starts
#1 Only
#1 Only, #2 Only, Auto, #1 Primary, #2 Primary
0
0 to 999999 hours
0
0 to 999999 hours
0
0 to 999999 starts
0
0 to 999999 starts
Disable
Disable, Enable
0 to 18°F (0 to 10°C)
9°F (5°C)
Off
Off, On
21