Operator Responsibilities
It is important that the operator become familiar with the
equipment and the system before attempting operation. During
the initial startup of the chiller, the Daikin Applied service
technician will be available to answer any questions and
instruct the proper operating procedures. It is recommended
that the operator maintain an operating log for each individual
chiller unit. In addition, a separate maintenance log should be
kept of the periodic maintenance and servicing activities.
Operator Schools
Training courses for Navigator
Maintenance and Operation are held throughout the year at the
Daikin Learning Institute in Verona, Virginia. The class includes
instruction on basic refrigeration, MicroTech
enhancing chiller efficiency and reliability, MicroTech
troubleshooting, system components, and other related
subjects. For more information, refer to the back cover of this
document for Training contact information.
MicroTech
III Unit Controller
®
Inputs/Outputs
Table 9: Analog Inputs
#
Description
AI1
Evap Entering Water Temp
AI2
Condenser Entering Water
Temp
X3
Demand Limit
X4
LWT Reset
X6
Evap Leaving Water Temp
Table 10: Analog Outputs
#
Description
X5
Cooling Tower VFD Speed
X7
Cooling Tower Bypass Valve Position 0-10VDC
Table 11: Digital Inputs
#
Description
DI1
Unit Ground Fault Relay
DI2
Evaporator Flow Switch
DI4
Remote Switch
DI5
Unit Switch
DI6
External Alarm
X1
Emergency Stop
X2
Mode Switch
X8
Condenser Flow Switch
IOM 1264-1 • NAVIGATOR
®
®
Water-cooled Screw
III controllers,
®
III
®
Signal Source
NTC 10KThermister
NTC 10KThermister
4-20 mA Current
4-20 mA Current
NTC 10KThermister
Output Signal
0-10VDC
Signal Off
Signal On
Fault
No Fault
No Flow
Flow
Unit disable
Unit enable
Unit disable
Unit enable
Unit disable
Unit enable
Unit off
Unit enable
Cool Mode
Ice Mode
No Flow
Flow
MODEL WWV CHILLERS
Table 12: Digital Outputs
#
Description
DO1
Evaporator Water Pump 1
DO2
Alarm Relay
DO3
Condenser Water Pump 1
DO5
Cooling Tower Fan 1
DO6
Cooling Tower Fan 2
DO9
Evaporator Water Pump 2
DO10
Condenser Water Pump 2
CC1 Module
Table 13: Analog Inputs
#
Description
X1
Discharge Temperature Circuit 1
X2
Evaporator Pressure Circuit 1
X3
Oil Pressure Circuit 1
X4
Condenser Pressure Circuit 1
X6
Condenser Leaving Water Temp
Table 14: Digital Outputs
#
Description
DO1
Oil Return Solenoid
Valve & Jet Pump
Solenoid Valve Circuit 1
DO3
VVR SV 1 Circuit 1
DO4
VVR SV 2 Circuit 1
DO5
VVR SV 3 Circuit 1
Evaporator EXV1 Module
Table 15: Analog Inputs
#
Description
X2
Suction Temperature Circuit 1
X3
Liquid Temperature Circuit 1
RapidRestore
Module
®
Table 16: Digital Inputs
#
Description
DI1
RapidRestore Unlock
Compressor VFD1 Module
Table 17: Analog Inputs
#
Description
50
Circuit 1 Motor Temperature
54
20
C
o
onTroller
peraTIon
Output OFF
Output ON
Pump Off
Pump On
Alarm not
Alarm Active
Active
Pump Off
Pump On
Off
On
Off
On
Pump Off
Pump On
Pump Off
Pump On
Signal Source
NTC 10k Thermister
Ratiometric 0.5-4.5 Vdc
Ratiometric 0.5-4.5 Vdc
Ratiometric 0.5-4.5 Vdc
NTC 10k Thermister
Output Off
Output On
Solenoid Closed
Solenoid Open
Solenoid Closed
Solenoid Open
Solenoid Closed
Solenoid Open
Solenoid Closed
Solenoid Open
Signal Source
NTC 10k Thermister
NTC 10k Thermister
Signal Off
Signal On
Lock Out Option
Unlock Option
Signal Source
PTC Thermister