Daikin Navigator WWV Installation, Operation And Maintenance Manual page 11

Water-cooled screw chillers. 120 to 300 tons (527 to 1055 kw) hfc-134a refrigerant 50/60 hz
Hide thumbs Also See for Navigator WWV:
Table of Contents

Advertisement

Table 3: Glycol Performance Factors
Freeze Point
%
°F
°C
Ethylene Glycol
10
26
-3.3
20
18
-7.8
30
7
-14
40
-7
-22
50
-28
-33
Propylene Glycol
10
26
-3.3
20
19
-7.2
30
9
-13
40
-5
-21
50
-27
-33
Ice Mode
Ice making chillers will run very cold fluid during off hours,
when energy is least expensive, to build a tank of ice. In ice
building mode, the unit will operate at full load until the shutoff
temperature setpoint is reached. Optional double evaporator
insulation is recommended for ice mode operation. The
standard controller software will require "ice" setpoint changes
and a digital signal into the controller is required to change to
the ice mode and back to standard cooling. Set points related
to ice mode can be found in
21
and wiring connection points are shown in
page
14.
Condenser Water Control
The minimum condenser inlet water temperature should not
be less than 60°F (15.6°C). If the water temperature is lower,
a method of condenser water temperature control will be
required. Cooling tower control is discussed beginning on
28.
Two-Way Bypass Valve Operation: A two-way regulating
control valve can control flow to ensure adequated condenser
water temperature. The unit controller can send a 0-10Vdc
signal to the valve to modulate its position.
Figure 4: Water Tower Connections - 2-Way Valve
www.DaikinApplied.com
Pressure
Flow
Drop
1.028
1.090
1.059
1.216
1.094
1.379
1.132
1.557
1.174
1.811
1.011
1.025
1.030
1.150
1.056
1.375
1.090
1.701
1.131
2.128
See Unit Level Set Points on page
Figure 10 on
I
nsTallaTIon and
Three-Way Bypass Valve Operation: To modulate the water
temperature in the condenser, install a three-way by-pass
valve.
Figure 5
shows how the three-way valve is applied in
the condenser water system. The three-way valve position can
be modulated by a 0-10Vdc signal from the unit controller to
regulates proper water temperature.
Figure 5: Water Tower Connections - 3-Way Valve
VFD Operating with a Condenser Water Pump: In place of a
valve, use a circulation pump controlled by an inverter.
The VFD speed may be controlled by an analog 0-10
Vdc signal issued by the controller according to the water
temperature entering the condenser.
Relief Valves
As a safety precaution and to meet code requirements, each
chiller is equipped with pressure relief valves located on the
condenser, evaporator, and compressor suction line(s) for the
purpose of relieving excessive refrigerant pressure (caused by
page
equipment malfunction, fire, etc.) to the atmosphere.
Table 4: Three-Way Relief Valve Data
Chiller
Relief Valve
Location
Pressure Setting (psi)
Discharge Cap.(lb/min air)
Qty
Connection Size
Building codes require that relief valves be vented to the
outside of a building. Relief piping connections to the relief
valves must have flexible connectors.
Remove plastic shipping plugs (if installed) from the inside of
the valves prior to making pipe connections. Whenever vent
piping is installed, the lines must be in accordance with local
11
IOM 1264-1 • NAVIGATOR
a
C
pplICaTIon
onsIderaTIons
WWV
Evaporator
Condenser
Top of vessel
Top of vessel
225
300
84.4
111
1 set
1 set
1.0-inch female
1.0-inch female
NPT
NPT
MODEL WWV CHILLERS
®

Hide quick links: