Refrigerant - Daikin RXF60B2V1B Installer's Reference Manual

R32 split series
Hide thumbs Also See for RXF60B2V1B:
Table of Contents

Advertisement

Ceiling-mounted
Wall-mounted
unit
unit
(a)
m (kg)
A
(m
)
m (kg)
2
min
≤1.842
≤1.842
1.843
3.64
1.843
2.0
3.95
2.0
2.2
4.34
2.2
2.4
4.74
2.4
2.6
5.13
2.6
2.8
5.53
2.8
3.0
5.92
3.0
3.2
6.48
3.2
3.4
7.32
3.4
3.6
8.20
3.6
3.8
9.14
3.8
4.0
10.1
4.0
4.2
11.2
4.2
4.4
12.3
4.4
4.6
13.4
4.6
4.8
14.6
4.8
5.0
15.8
5.0
5.2
17.1
5.2
5.4
18.5
5.4
5.6
5.6
19.9
5.8
5.8
21.3
6.0
6.0
22.8
6.2
6.2
24.3
6.4
6.4
25.9
6.6
6.6
27.6
6.8
6.8
29.3
7.0
31.0
7.0
7.2
32.8
7.2
7.4
34.7
7.4
7.6
36.6
7.6
7.8
38.5
7.8
7.956
40.1
7.956
m
Total refrigerant charge in the system
A
Minimum floor area
min
(a)
Ceiling-mounted unit (= Ceiling-mounted unit)
(b)
Wall-mounted unit (= Wall-mounted unit)
(c)
Floor-standing unit (= Floor-standing unit)
1.2.3

Refrigerant

If applicable. See the installation manual or installer reference guide
of your application for more information.
NOTICE
Make sure refrigerant piping installation complies with
applicable legislation. In Europe, EN378 is the applicable
standard.
NOTICE
Make sure the field piping and connections are NOT
subjected to stress.
WARNING
During tests, NEVER pressurize the product with a
pressure higher than the maximum allowable pressure (as
indicated on the nameplate of the unit).
WARNING
Take sufficient precautions in case of refrigerant leakage. If
refrigerant gas leaks, ventilate the area immediately.
Possible risks:
▪ Excessive refrigerant concentrations in a closed room
can lead to oxygen deficiency.
▪ Toxic gas may be produced if refrigerant gas comes
into contact with fire.
RXF50+60B2_RXF71A2_RXP50~71L2_(A)RXM42~71N2_RXJ50N2_
RXA42+50B2
R32 split series
4P513661-6B – 2018.05
Floor-standing
unit
(b)
(c)
A
(m
)
m (kg)
A
(m
2
2
min
min
≤1.842
1.843
28.9
4.45
2.0
34.0
4.83
5.31
2.2
41.2
5.79
2.4
49.0
6.39
2.6
57.5
7.41
2.8
66.7
8.51
3.0
76.6
9.68
3.2
87.2
10.9
3.4
98.4
12.3
3.6
110
13.7
3.8
123
15.1
4.0
136
16.7
4.2
150
18.3
4.4
165
20.0
4.6
180
21.8
4.8
196
23.6
5.0
213
25.6
5.2
230
27.6
5.4
248
29.7
5.6
267
31.8
5.8
286
34.0
6.0
306
36.4
6.2
327
38.7
6.4
349
41.2
6.6
371
43.7
6.8
394
7.0
417
46.3
7.2
441
49.0
51.8
7.4
466
54.6
7.6
492
57.5
7.8
518
59.9
7.956
539
1 General safety precautions
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump
)
down the system, and there is a leak in the refrigerant
circuit:
▪ Do NOT use the unit's automatic pump down function,
with which you can collect all refrigerant from the
system into the outdoor unit. Possible consequence:
Self-combustion and explosion of the compressor
because of air going into the operating compressor.
▪ Use a separate recovery system so that the unit's
compressor does NOT have to operate.
WARNING
ALWAYS recover the refrigerant. Do NOT release them
directly into the environment. Use a vacuum pump to
evacuate the installation.
NOTICE
After all the piping has been connected, make sure there is
no gas leak. Use nitrogen to perform a gas leak detection.
NOTICE
▪ To avoid compressor breakdown, do NOT charge more
than the specified amount of refrigerant.
▪ When the refrigerant system is to be opened,
refrigerant MUST be treated according to the applicable
legislation.
WARNING
Make sure there is no oxygen in the system. Refrigerant
may only be charged after performing the leak test and the
vacuum drying.
▪ In case re-charge is required, refer to the nameplate of the unit. It
states the type of refrigerant and necessary amount.
▪ The unit is factory charged with refrigerant and depending on pipe
sizes and pipe lengths some systems require additional charging
of refrigerant.
▪ Only use tools exclusively for the refrigerant type used in the
system, this to ensure pressure resistance and prevent foreign
materials from entering into the system.
▪ Charge the liquid refrigerant as follows:
If
A siphon tube is present
(i.e., the cylinder is marked with
"Liquid filling siphon attached")
A siphon tube is NOT present
▪ Open refrigerant cylinders slowly.
▪ Charge the refrigerant in liquid form. Adding it in gas form may
prevent normal operation.
Then
Charge with the cylinder upright.
Charge with the cylinder upside
down.
Installer reference guide
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents