Page 2
The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein.
Page 3
• Maintenance: To clean the indoor unit heat exchanger in extreme condition added. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 4
• Indoor unit fan motor: Checking and repair procedures for new models added. • Wifi control PCB: Checking and repair procedures added. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Indicates a situation that could result in minor or moderate injury. NOTICE Indicates a situation that could result in equipment or property damage. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
WARNING Improper installation or attachment of equipment or accessories could result in electrical shock, short-circuit, leaks, fire or other damage to the equipment. ONLY use accessories, optional equipment and spare parts made or approved by Daikin unless otherwise specified. WARNING...
Page 9
WARNING Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the Daikin documentation). WARNING Make sure the work site environment is clean and safe to work in. Beware of spilled fluids, like water, oil or other substances.
Page 10
In case of R32 (HFC) refrigerant, any flame in contact with (leaking) refrigerant is extremely dangerous. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 11
▪ Make sure all covers are closed before starting up the unit. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 12
All maintenance staff and others working in the local area MUST be instructed on the nature of work being carried out. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 13
Make sure the ventilation machinery and outlets are operating adequately and are NOT obstructed. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
NOTICE Make sure the field piping and connections are NOT subjected to stress. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
When the power turns back on after a power break, the previously selected mode will be resumed. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
4 Perform a check of the indoor unit main PCB. See "3.7 Indoor unit main PCB" [ 84]. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
If all procedures listed above have been performed and the problem is still present, contact the helpdesk. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
If all procedures listed above have been performed and the problem is still present, contact the helpdesk. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Possible cause: Outdoor temperature is out of operation range. 2 Perform a check of the compressor. See "3.2 Compressor" [ 54]. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
If all procedures listed above have been performed and the problem is still present, contact the helpdesk. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
▪ Faulty or disturbance of the power supply (power supply MUST be within range of nominal operating voltage ±4%), ▪ Power drop, ▪ Short circuit. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
If all procedures listed above have been performed and the problem is still present, contact the helpdesk. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
If all procedures listed above have been performed and the problem is still present, contact the helpdesk. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Possible cause: Faulty wiring between the outdoor unit and the indoor unit. 3 Perform a check of the main PCB. See "3.8 Main PCB" [ 89]. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
"3.7 Indoor unit main PCB" [ 84]. Possible cause: Faulty indoor unit main PCB. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 38
If all procedures listed above have been performed and the problem is still present, contact the helpdesk. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
A power failure of 2 to 10 cycles stops a power failure. air conditioner operation. Check the power supply. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
1787 Ω ± 10% Is the measured value correct? Action Continue with the next step. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 48
See the databook on Business Portal for the temperature range of the operation modes. 1 Connect the 4‑way valve connector to the appropriate PCB. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 49
185]). Is the flow correct? Action Skip the next step of this procedure. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 50
(suction, discharge). Compare with normal operation conditions of the unit. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
4‑way valve pipes using an oxygen acetylene torch and remove the 4‑way valve pipes from the refrigerant pipes using pliers. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 52
4‑way valve and solder the 4‑way valve pipes to the refrigerant pipes. a 4‑way valve pipe b 4‑way valve c Putty d Insulation (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 53
Return to the troubleshooting of the specific error and continue with the next procedure. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure the rectifier voltage is below 10 V DC before proceeding. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 55
10 V DC before proceeding. 2 Remove the cover of the compressor wire terminals. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 56
4 Measure the resistance between the compressor motor windings U-V, V-W and U-W. Result: All measurements MUST be approximately the same. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 57
W. ALWAYS measure at the PCB side. Result: All measurements MUST be the same. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 58
Note the position of the Faston connectors on the compressor wire terminals to allow correct connection during installation. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
10 V DC before proceeding. 2 Remove the cover of the compressor wire terminals. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 60
7 Supply nitrogen to the refrigerant circuit. The nitrogen pressure MUST NOT exceed 0.02 MPa. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 61
13 Install plugs or caps on the open pipe ends of the refrigerant piping to avoid dirt or impurities from entering the piping. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 62
8 Wrap a wet rag around the compressor pipes and any other components near the compressor and solder the compressor pipes to the refrigerant pipes. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 63
W Wire terminal W 12 Install the cover of the compressor wire terminals. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
2 Fill the refrigerant circuit with nitrogen until pressurized just below operating pressure of the high pressure switch. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 78
7 Lower the pressure of the nitrogen in the refrigerant circuit just above reset pressure of the high pressure switch. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
4 Check the diode module by measuring the voltage between the following pins of the DC fan motor connector. Comm Voltage 0.992 V DC (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
(if installed) on the right hand side of the fan motor cover for easier removal. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 83
Return to the troubleshooting of the specific error and continue with the next procedure. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
See "To check the power supply to the indoor unit" ("4.1.2 Repair procedures" [ 154]) for the next steps. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 85
1 Measure the continuity of the fuse. If no continuity is measured, the fuse has blown. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
To remove the indoor unit main PCB Prerequisite: Stop the unit operation via the user interface. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 87
NOT apply force, as this may damage the connector or connector pins of the PCB. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 88
Make sure the fuse is plugged‑in correctly (contact with the fuse holder). a Fuse Is the problem solved? Action No further actions required. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Continue with the next step. 3 Check the power supply to the unit, see "4.1.1 Checking procedures" [ 153]. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 90
Prerequisite: First check the power supply to the main PCB, see "Checking procedures" [ 89]. 1 Locate the HAP LED on the main PCB. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 91
Prerequisite: First perform all earlier main PCB checks, see "Checking procedures" [ 89]. 1 Visit your local spare parts webbank. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 92
3 Disconnect the wiring from the compressor wire terminals U, V and W. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 94
1 Measure the continuity of the fuse. If no continuity is measured, the fuse has blown. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 95
A (A)RXF20~35A + RXF20+25B + (A)RXF20~42C + (A)RXF42D units a + terminal b – terminal (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 96
3 Check the diode module in reference with the image and the table below. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 97
4 If the diode module is NOT OK, replace the main PCB, see "Repair procedures" [ 101]. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 98
A (A)RXF20~35A + RXF20+25B + (A)RXF20~42C + (A)RXF42D units d DC+ e DC– (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 99
2 Check the power module IPM2 in reference with the image and the table below. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 100
0.475 V 0.475 V 0.475 V DC– 0.475 V DC– (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 101
2 Disconnect the power supply wires from the main power supply terminal X1M. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 102
1 Disconnect all connectors and Faston connectors from the main PCB. a Screw b PCB support (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 103
1 Apply grease to the PCB contact surface of the heat sink. Distribute the grease as evenly as possible. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 104
Prerequisite: Remove the required plate work, see "3.10 Plate work" [ 124]. 1 Remove the fuse from the PCB. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 105
Return to "Checking procedures" [ 89] of the PCB and continue with the next procedure. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Prerequisite: First check the power supply to the main PCB, see "Checking procedures" [ 106]. 1 Locate the HAP LED on the main PCB. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 107
Prerequisite: Stop the unit operation via the user interface. 1 Turn OFF the respective circuit breaker. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 108
Prerequisite: First perform all earlier main PCB checks, see "Checking procedures" [ 106]. 1 Turn ON the power of the unit. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 109
3 Check the diode module in reference with the image and the table below. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 110
2 Check the power module IPM1 in reference with the image and the table below. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 111
To remove the main PCB Prerequisite: Stop the unit operation via the user interface. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 112
ALWAYS apply new grease on the PCB heat sink. NOT doing so may cause the PCB to fail due to insufficient cooling. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 113
Return to "Checking procedures" [ 106] of the PCB and continue with the next procedure. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
1 First perform a mechanical check of the DC fan motor assembly, see "Checking procedures" [ 114]. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 115
Replace the DC fan motor, see "Repair procedures" [ 117]. 9 Turn ON the power of the unit. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 116
5 Turn OFF the unit via the user interface. 6 Turn OFF the respective circuit breaker. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 117
124]. 2 Remove the nut that fixes the propeller fan blade assembly. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 118
1 Install the propeller fan blade assembly on the DC fan motor assembly. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Is the propeller fan blade assembly Action damaged? Replace the propeller fan blade assembly, see "Repair procedures" [ 122]. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 120
6 Turn OFF the unit via the user interface. 7 Turn OFF the respective circuit breaker. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 121
13 Connect the DC fan motor connector to the PCB. Remove the plastic insert from the connector for easier measurement. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 122
3 Pull and remove the propeller fan blade assembly from the DC fan motor assembly. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 123
2 Install and tighten the nut to fix the propeller fan blade assembly. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
To remove the refrigerant connection cover DANGER: RISK OF ELECTROCUTION DANGER: RISK OF BURNING/SCALDING 1× (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 125
2 Loosen and remove the screws that fix the top plate. a Screw b Top plate 3 Remove the top plate. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 126
124]. 1 Remove the insulation on the upper side of the switch box. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 127
Right side plate assembly 4 Remove the screws that fix the wire clamp. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 128
2 Install the right side plate assembly on the outdoor unit and fix it using the screws. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 129
6 Fix the wiring to the switch box using a new cable tie. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
1 Hold the front panel by the panel tabs on both sides and open it. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 131
3 Push down the 3 upper hooks marked with a symbol with 3 circles. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 132
Prerequisite: Remove the front grille. 1 Remove 1 screw from the electrical wiring box. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 133
5 Disconnect the connectors of the indoor unit fan motor, the swing flap motor and the swing raster motor (if equipped) from the indoor unit PCB. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 134
1 Attach the front panel. Align the shafts with the slots and push them all the way in. 2 Close the front panel, see "3.10 Plate work" [ 124]. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 136
4 Measure the inductance of the reactor using an LCR meter. Result: The inductance MUST be as follows: (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
1 Remove both swing flaps from the indoor unit (by clicking it out). 2 Remove the cover. a Cover b Screw c Swing flap motor (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
The thermistors may vary according to the specific unit. 3 Determine the thermistor resistance that matches the measured temperature. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 148
5 Check that the measured resistance value matches the resistance determined through the measured temperature (earlier step in the procedure). E.g: (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
3 Measure the power supply voltage between the pins 4‑5 on the wifi control PCB connector. Result: The measured voltage MUST be 10~16 V DC. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
2 Carefully click the complete wifi control PCB assembly out of the indoor unit. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 151
2 Disconnect the wiring harness connector from the indoor unit main PCB. 3 Cut all tie straps (if any) that fix the wiring harness. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 152
Return to the troubleshooting of the specific error and continue with the next procedure. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Return to the troubleshooting of the specific error and continue with the next procedure. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Return to the troubleshooting of the specific error and continue with the next procedure. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 156
Due to the relationship to pressure control and electronic expansion valve control, the amount of refrigerant needs to be examined according to operating conditions. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 162
MUST be reached to allow the evaporation of the moisture will need (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Wait for the outdoor temperature to return within the operating range. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 164
Return to the troubleshooting of the specific error and continue with the next procedure. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
General maintenance/inspection checklist. Next to the maintenance instructions in this chapter, a general maintenance/inspection checklist is also available on the Daikin Business Portal (authentication required). The general maintenance/inspection checklist is complementary to the instructions in this chapter and can be used as a guideline and reporting template during maintenance.
3 Wash the air filters with water or clean them with a vacuum cleaner. 4 Soak in lukewarm water for about 10 to 15 minutes. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 167
Return to the troubleshooting of the specific error and continue with the next procedure. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
When the main power is turned off and then back on again, operation will resume automatically. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 173
When the main power is turned off and then back on again, operation will resume automatically. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Correct diagrams are supplied with the unit and can also be found in the technical data book. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 186
Correct diagrams are supplied with the unit and can also be found in the technical data book. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 187
Correct diagrams are supplied with the unit and can also be found in the technical data book. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 188
Correct diagrams are supplied with the unit and can also be found in the technical data book. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 189
Correct diagrams are supplied with the unit and can also be found in the technical data book. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 190
Correct diagrams are supplied with the unit and can also be found in the technical data book. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Correct diagrams are supplied with the unit and can also be found in the technical data book. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 192
Correct diagrams are supplied with the unit and can also be found in the technical data book. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 193
Correct diagrams are supplied with the unit and can also be found in the technical data book. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 194
Correct diagrams are supplied with the unit and can also be found in the technical data book. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 195
Correct diagrams are supplied with the unit and can also be found in the technical data book. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 196
Correct diagrams are supplied with the unit and can also be found in the technical data book. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 197
Correct diagrams are supplied with the unit and can also be found in the technical data book. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 198
Correct diagrams are supplied with the unit and can also be found in the technical data book. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Technical data 6.5 Field information report See next page. (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 202
In case a problem occurred on the unit which could not be resolved by using the content of this service manual or in case you have a problem which could be resolved but of which the manufacturer should be notified, we advise you to contact your distributor.
Page 203
Application information Application (house, apartment, office,…): New project or reimbursement: Heat emitters (radiators / under floor heating / fan coils /…): Hydraulic layout (simple schematic): Unit / Installation information Model name: Serial number: Installation / commissioning date: Software version hydro PCB A1P Software version hydro PCB A5P Software version user interface: Software version outdoor PCB:...
Technical data 6.6 Service tools 1 For an overview of the available service tools, check the Daikin Business Portal (authentication required). 2 Go to the tab After-sales support on the left navigation pane and select Technical support. 3 Click the button Service tools. An overview of the available service tools for the different products is shown.
▪ J11: Protection for error memory overwrite (only to be used during development) ▪ J12: No function for this unit (A)(F)TXF20~71A + FTXF20~25B + (A)(F)TXF20~42C + (A)(F)TXF20~42D + Service manual (A)(F)TXF20~42E + (A)RXF20~71A + RXF20~60B + (A)RXF20~42C + (A)RXF20~42D + (A)RXF20~42E Split Sensira R32 ESIE18-12G – 2023.01...
Page 208
ESIE18-12G 2023.01 Verantwortung für Energie und Umwelt...