Additional Installation Site Requirements Of The Outdoor Unit In Cold Climates; Preparing Refrigerant Piping; Refrigerant Piping Requirements; Refrigerant Piping Length And Height Difference - Daikin RXF60B2V1B Installer's Reference Manual

R32 split series
Hide thumbs Also See for RXF60B2V1B:
Table of Contents

Advertisement

5 Preparation
Install the outdoor unit away from direct sea winds.
Example: Behind the building.
a
If the outdoor unit is exposed to direct sea winds, install a
windbreaker.
▪ Height of windbreaker≥1.5×height of outdoor unit
▪ Mind the service space requirements when installing the
windbreaker.
a
d
c
a
Sea wind
b
Building
c
Outdoor unit
d
Windbreaker
The outdoor unit is designed for outdoor installation only, and for
ambient temperatures ranging from –10 to 46°C in cooling mode and
from –15 to 24°C in heating mode.
5.2.2
Additional installation site requirements
of the outdoor unit in cold climates
Protect the outdoor unit against direct snowfall and take care that the
outdoor unit is NEVER snowed up.
c
a
Snow cover or shed
b
Pedestal
c
Prevailing wind direction
d
Air outlet
Installer reference guide
10
b
c
d
c
b
a
c
b
In any case, provide at least 300  mm of free space below the unit.
Additionally, make sure the unit is positioned at least 100 mm above
the maximum expected level of snow. See
outdoor unit" on page 11
for more details.
In heavy snowfall areas it is very important to select an installation
site where the snow will NOT affect the unit. If lateral snowfall is
possible, make sure that the heat exchanger coil is NOT affected by
the snow. If necessary, install a snow cover or shed and a pedestal.
5.3

Preparing refrigerant piping

5.3.1

Refrigerant piping requirements

INFORMATION
Also read the precautions and requirements in the
"General safety precautions" chapter.
▪ Piping material: Phosphoric acid deoxidised seamless copper.
▪ Piping diameter:
Class 42~60
Liquid piping
Ø6.4 mm (1/4")
Gas piping
Ø12.7 mm (1/2")
▪ Piping temper grade and thickness:
Outer diameter
Temper grade
(Ø)
6.4 mm (1/4")
Annealed (O)
12.7 mm (1/2")
15.9 mm (5/8")
Annealed (O)
(a)
Depending on the applicable legislation and the unit's
maximum working pressure (see "PS High" on the unit
name plate), larger piping thickness might be required.
5.3.2
Refrigerant piping length and height
difference
What?
Maximum allowable pipe length
Minimum allowable pipe length
Maximum allowable height distance
5.3.3

Refrigerant piping insulation

▪ Use polyethylene foam as insulation material:
▪ with a heat transfer rate between 0.041 and 0.052 W/mK (0.035
and 0.045 kcal/mh°C)
▪ with a heat resistance of at least 120°C
▪ Insulation thickness
Pipe outer diameter
Insulation inner
)
diameter (Ø
p
6.4 mm (1/4")
8~10 mm
12.7 mm (1/2")
14~16 mm
15.9 mm (5/8")
16~20 mm
Ø
Ø
i
i
Ø
Ø
p
p
t
If the temperature is higher than 30°C and the humidity is higher
than RH 80%, the thickness of the insulation materials should be at
least 20  mm to prevent condensation on the surface of the
insulation.
RXF50+60B2_RXF71A2_RXP50~71L2_(A)RXM42~71N2_RXJ50N2_
"6.3  Mounting the
Class 71
Ø15.9 mm (5/8")
(a)
Thickness (t)
Ø
≥0.8 mm
t
≥1.0 mm
Distance
30 m
3 m
20 m
Insulation thickness
)
(t)
i
≥10 mm
≥10 mm
≥13 mm
RXA42+50B2
R32 split series
4P513661-6B – 2018.05

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents