Download Print this page

Description Of Unit - Bosch MDCI20-3 User Manual

Climate 5000 vrf mdci series all dc inverter outdoor units (three phase)
Hide thumbs Also See for MDCI20-3:

Advertisement

4 | DESCRIPTION OF UNIT

Ensure hands are free from contaminants and are dry prior to performing
any electrical maintenance work.
Do not touch the heat exchanger fins.
These fins are sharp and could cause injury. If the fins are damaged, this will
affect the heat exchange performance.
Do not place items which might be damaged by moisture under the
indoor unit.
Condensation may form if the humidity is above 80%, the drain outlet is
blocked or the filter is dirty.
Ensure condense drainage has a consistent fall away from the unit.
Ensure you do not touch internal parts of the controller.
This could result in serious injury.
Do not use air conditioner where chemicals or gases can affect your
health.
This appliance should only be used by a competent person. Failure to
comply with these instructions may cause serious injury or damage.
When the total capacity of the indoor unit exceeds 100%, ensure the
indoor unit is attenuated.
When the capacity of the indoor unit is greater than or equal to the sum
of 120%, in order to ensure effectiveness of the indoor unit, ensure you
turn the indoor unit on one at a time.
The outdoor unit should be maintained periodically to ensure long life
span of the equipment.
6 720 862 442 (2016/04)
Ensure the communication signal wires do not touch bare copper pipe-
work. The refrigerant circuit will get hot and melt the cables.
2. DESCRIPTION OF UNIT
The air conditioning system consists of an outdoor unit, indoor
units, connective pipework and a way of controlling the system
(remote controller). (see Fig. 1)
Force Cooling Control
Force cooling control
Button sw1
sw1 sw2
Force Cooling Control
Force cooling control of the outdoor unit is to be pressed when test running.
The unit will start in cooling and once the outdoor unit changes to 62 Hz the
running of the indoor unit will run in high speed. Press the button again to exit
forced cooling mode.
Display function
SW2 on the main control board of the outdoor unit is the inspection function
button (as shown in Figure 2-1). Pressing this button once displays the first
parameter.
Additional button presses will display other parameters following the
sequence shown in Table 2-1.
Table 2-1
Sequence
Displayed content
1
0--
2
1--
3
2--
4
3--
5
4--
6
5--
7
6--
8
7--
9
8--
9--
10
11
0--
12
1--
13
2--
14
3--
15
4--
5--
16
17
6--
18
7--
19
8--
20
9--
MDCI Series – All DC Inverter Outdoor Units (Three phase)
Display control
button sw2
MAIN BOARD
(OUTDOOR UNIT)
Fig. 2-1
Normal display
Current frequency
Local capacity of outdoor units
Total capacity requirements of
outdoor units
Total requirements of outdoor units
corrected capacity
Operating mode
Operating FAN speed and FAN
grade
T2B/T2 average temperature
T3 pipe temperature
T4 environment temperature
Inverter exhaust temperature
Non-inverter exhaust temperature
(reserved)
Heat dissipator surface
temperature (reserved)
Electronic expansion valve
aperture
Inverter input current
Non-inverter input current
Exhaust pressure (reserved)
Priority mode
Indoor unit quantity
Quantity of working indoor units
Last fault or protection code
--

Hide quick links:

Advertisement

loading
Need help?

Need help?

Do you have a question about the MDCI20-3 and is the answer not in the manual?

This manual is also suitable for:

Mdci26-3Mdci22-3