Verify Switching Between Operation Modes - Liebert NX series Operation & Maintenance Manual

10-30kva 208v, 60hz
Table of Contents

Advertisement

4. Turn the rotary switch to BYPASS.
#
Indicator
1
Rectifier indicator
2
Battery indicator
3
Bypass indicator
4
Inverter indicator
5
Load indicator
6
Alarm indicator
The maintenance switch SW1-D opens and output switch SW1-A closes. The UPS powers from
static bypass instead of from maintenance bypass. The bypass and load indicators turn on. The
design of the rotary switch ensures uninterrupted output.
5. Turn the rotary switch to NORMAL, then press the INVERTER ON control button for 2 seconds.
The inverter will start and the inverter indicator will flash green. After the inverter is ready, the
UPS transfers from bypass to inverter, the bypass indicator turns off and the inverter and load
indicators turn on.
The UPS is operating normally. The UPS Mimic display indicators will:
#
Indicator
1
Rectifier indicator
2
Battery indicator
3
Bypass indicator
4
Inverter indicator
5
Output indicator
6
Alarm indicator
3.2.2

Verify Switching Between Operation Modes

Switch from Normal Mode to Battery Mode
• Open CB1 to enter battery mode. This breaks the utility connection to the NX.
To return to normal mode, close CB1 after a few seconds. The rectifier will restart automatically
after 10 seconds and resume feeding power to the inverter.
Switch from Normal Mode to Bypass Mode
• Press INVERTER OFF button to switch to bypass mode.
NOTE
In bypass mode, the load is being powered by the utility and is not receiving conditioned power
through the rectifier.
Switch from Bypass Mode to Normal Mode
• Turn the rotary switch to NORMAL.
• In bypass mode, press the INVERTER ON button. When the rectifier is ready, the UPS will
switch to normal mode.